Manual

Technical Data
6-2
Positioner SIPART PS2/SIPART PS2 PA
C79000-G7476-C150–01
General data: basic instrument 6DR400x–xx and 6DR410x–xx
AD converter
Sampling time 12.5 ms
Resolution v 0.05 %
Transmission error v 0.2 %
Temperature influence v 0.1 % / 10 K
Controller data
5–step switch adaptive
Dead zone dEbA = Auto adaptive or
dEbA = 0.1 to 10 % fixed setting
Controllable actuating times w 1.5 s
Pneumatic and mechanical data: basic instrument 6DR400x–xx and 6DR410x–xx
Power supply (inlet air)
Medium Instrument air, free of oil, water, and dust
Pressure 1.4 to 7 bar
Solids content < 30 µm
Dewpoint 20 K below the lowest ambient temperature
Unrestricted flow
Inlet air valve 5.5 Nm
3
/h with a drop in pressure from 6 to
5 bar
Valve leakage < 6 10
–4
Nm
3
/h
Restrictor ratio adjustable up to : 1
Air consumption in settled state < 3.6 10
–2
Nm
3
/h
Types of actuators Single and double acting (not with
6DR4001–xx)
Positioning times 1.5 to 150 s
Linear actuators
Mounting kit 6DR4004–8V and –8L acc. to IEC 534–6 (NAMUR)
Linear range 3 to 130 mm (rotation angle on the controller
output axis from 16° to 90°)
Rotary actuators
Mounting kit 6DR4004–8D
Angle of rotation 30° to 100°