3.5 Pneumatic connection
!
Warning
For safety reasons the pneumatic power must only be input after
installation when the positioner is switched to operating level P manual
mode with the electrical signal applied (state of supply, see Fig. 4-2).
Note
Check the air quality! Industrial air, free of oil, solid content < 30 mm, dew
point under pressure 20 K below the lowest ambient temperature.
If necessary connect the manometer block for inlet air pressure and
positioning pressure.
Connection using inside thread G 1/4 DIN 45141:
P
Z
inlet air 1.4 to 7 bar
Y1 positioning pressure 1 for single and double-acting actuators
Y2 positioning pressure 2 for double-acting actuators
E air outlet (remove silencer if necessary)
Safety position in the event of electrical power failure
single acting: Y1 vented
double acting: Y1 max. positioning pressure
(inlet air pressure)
Y2 vented
Connect positioning pressures Y1 and Y2 (only for double-acting
actuators) in accordance with the required safety position.
Connect the inlet air to P
Z
.