Owner's manual

Moniteur
Installation and Operating Instructions
VPT Series - Sentinel S3
II 2 D Ex tb IIIC T85°C, IP66/67
II 2 G Ex d IIB +H2 T6, IP66/67
Cl. I, Div. 1, Groups B, C, D
Cl. II, Div. 1, Groups E, F, G
Hazardous Area Ratings - ATEX / IECEx
Hazardous Area Ratings - North America
FM09ATEX0020X
IECEx FMG 09.0002X
Alternate: Cl. I, Div. 1, Groups C, D
Cl. II, Div. 1, Groups E, F, G
MOUNTING THE DEVICE TO YOUR ACTUATOR
1. Select the proper mounting bracket kit to mount the
device to your actuator or valve.
2. First mount the bracket to the device with the
hardware provided.
3. Attach the assembly to the actuator or valve.
SETTING OF SWITCHES / SENSORS
1. Loosen the cover screws and remove the cover.
Move the valve or valve actuator assembly to the
closed position.
2. Determine which switch is to be set. Move the
corresponding cam as required until the switch
or sensor is actuated.
3. Move the valve or valve actuator assembly
to the open position and repeat step 2.
4. Replace the cover and tighten the screws.
SETTING OF VISUAL INDICATOR
1. The Moniteur Visual Indicator is 100% adjustable to any
valve position. To adjust the indicator, remove the clear
cover by turning it counter-clockwise to disengage the
breach lock and then lift it off.
2. Remove the internal indicator portion to reveal the
adjusting ring. Loosen the ring screws, adjust the ring,
re-tighten the screws and replace the indicator.
3. For additional adjustment, the ring screws can be
removed and the ring rotated 45°, revealing additional
adjusting ring threads.
4. Replace clear cover.
M O N I T E U R D E V I C E S I N C O R P O R A T E D
3 6 C o m m e rc e R o a d , C e d a r G ro v e , N J 0 7 0 0 9 Te l . ( 9 7 3 ) 8 5 7 - 1 6 0 0 Fa x ( 9 7 3 ) 8 5 7 - 7 2 8 9
w w w . m o n i t e u r d e v i c e s . c o m
Operating Temperature (deg. C) -40° to 79°
WIRING OF VALVE POSITION TRANSMITTER
All wiring shall be done according to the specific wiring
diagram located inside the cover. All field wiring shall be
done according to site, local and national electrical codes.
Be sure to secure all the appropriate connections including
the ground. Supply connection wire shall be rated to at least
10°C above the rated ambient temperature of 80°C.
OPEN
MONITEUR
MONITEUR
A
B
C
CONDUIT CONNECTIONS A, B, C
Conduit
Code
0
5
A
B
E
F
Conduit
A
3/4” NPT
3/4” NPT
M20
M20
M25
M25
Conduit
B
n/a
3/4” NPT
n/a
M20
n/a
M25
Conduit
C
3/4” NPT
3/4” NPT
M20
M20
M25
M25
WARNING: Unused conduit entries shall be
closed with suitable certified plugs to
maintain the enclosure type of protection
Form IO-S3A-EN Rev. B Page 1
ATEX:
EN 60079-0: 2009
EN 60079-1: 2007
EN 60079-31: 2009
EN 60529: 1991; +A1:2000
IECEx:
IEC 60079-0: 2007
IEC 60079-1: 2007
IEC 60529: 2001
Standards
Alert: Read completely these instructions
before using this device. Follow all warnings,
cautions and instructions explicitly.
CAUTION: To reduce the risk of ignition of
hazardous atmospheres, disconnect the device
from the supply circuit before opening. Keep
assembly tightly closed during operation.
½”NPT Male and Female
Conduits are also available
Please check nameplate for actual ratings.
TYPE 4X IP66/67

Summary of content (2 pages)