MOTOR PROTECTION ATCDIVERSIFIED.
PRA-100-AFA PRA-100-AFN PRA-100-AFE SLA-120-AFN SLA-120-ALA Motor-Driven Cycle Progress Timer SLA-120-ALE SLA-120-ALER SLA-120-ASA PHASE VOLTAGE MONITORS SLA-120-ASB SLA-208-AFN SLA-220-AFN SLA-230-ALA SLA-230-ALE SLA-230-ALER SLA-230-ASA SLA-230-ASB SLA-240-AFN SLA-380-ALE SLA-380-ALER SLA-380-ASA SLA-440-AFE SLA-440-ALE SLA-440-ALER SLA-440-ASA SLA-460-AFE SLA-480-AFE SLA-575-AFE SLA-575-ALE SUA-120-ALA SUA-120-ALAU SUA-230-ALA SUA-230-ALAU SUA-380-ASA SUA-440-ASA All models available with fixed oper
80 440 460 480 575 Feature Matrix 240 UL LISTED 230 CONTROL VOLTAGE REQUIRED 220 LED INDICATOR 208 MANUAL 120 AUTOMATIC RESET NOMINAL LINE VOLTAGE PHASE-TO-PHASE 50/60 HZ STYLE E ADJUSTABLE DELAY PHASE SEQUENCE PHASE UNBALANCE OVER VOLTAGE UNDER VOLTAGE MODEL NUMBER PHASE LOSS feature matrix PBC-120-ALE PBC-230-ALE PBC-400-ALE PBC-440-ALE PBC-480-ALE PBC-575-ALE PBC-120/208-ALE PBC-220/380-ALE PBC-277/480-ALE PHASE VOLTAGE MONITORS PBD-120-ALE PBD-230-ALE PBD-400-ALE PBD-440-ALE
SLD-120-ALE SLD-120-ASA SLD-230-ALE SLD-230-ASA Motor-Driven Cycle Progress Timer SLD-380-ALE SLD-380-ASA SLD-440-ALE PHASE VOLTAGE MONITORS SLD-440-ASA SLE-120-ALE SLE-230-ALE SLE-380-ALE SLE-440-ALE SLH-120-ALE SLH-230-ALE SLH-440-ALE SLJ-120-ALE SLJ-230-ALE SLJ-380-ALE SLJ-440-ALE SLM-120-ASE SLM-230-ASE SLM-380-ASE SLM-440-ASE SLM-575-ASE SLU-100-ASA SLU-100-ASD SLU-600-ASTDS MPA-1000 MPA-1100 138 Diversified Electronics 800.727.5646 atcdiversified.com CURRENT: OVER/UNDER/UNBAL.
Feature Matrix CSA CERTIFIED UL RECOGNIZED LED INDICATOR STYLE N STYLE E STYLE A 440 VAC 240 VAC 230 VAC ENCLOSURE 220 VAC 208 VAC 120 VAC 110 VDC 48 VDC 28 VDC 24 VDC 24 VAC 12 VDC NOMINAL LINE VOLTAGE ADJUSTMENT–FIXED ADJUSTMENT–LOCKNUT ADJUSTMENT–KNOB OVER VOLTAGE MODEL NUMBER UNDER VOLTAGE feature matrix UOA-12-D*A UOA-24-A*A UOA-24-D*A UOA-48-D*A Motor-Driven Cycle Progress Timer UOA-110-D*A UOA-120-A*A UOA-120-AFN UOA-208-A*A PHASE VOLTAGE MONITORS UOA-208-AFN UOA-220-AF
SLU-100 Series Phase Monitor Relays (3-Phase Monitors) provide cost-effective protection against premature equipment failure caused by voltage faults on 3-Phase systems (Wye or Delta). The SLU Series multi-mode phase monitoring relay, was designed for the convenience of electrician's, maintenance managers and engineers.
SLU-600 Series The ATC-Diversified Electronics SLU-600-ASTDS Universal Phase Monitor protects 3-phase motors up to 700VAC. The Rapid Cycling feature prevents motors cycling due to load-induced line fault conditions. Powered by 120VAC, this reliable motor protection relay is unaffected by transients and disturbances from the monitored power source. The SLU-600 Series is UL Listed under UL File Number E55826.
SLU-600 Series (inches/millimeters) PHASE VOLTAGE MONITORS dimensions top label LED STATUS CHART = OFF = ON = FLASHING Unbal & Ø Normal Under Red Over Red Loss Red Green LED LED LED LED Powering Up/First 3 Sec Powered Up/Normal Voltages Relay ON/Under Voltage Detected/FAULT DELAY active Relay ON/Over Voltage Detected/ FAULT DELAY active Relay ON/Unbal or Ø Loss Detected/FAULT DELAY active Relay OFF/Under Voltage Failure Relay OFF/Over Voltage Failure Relay OFF/Unbal or Ø Loss Failure Relay OFF/Under
MPA Series The MotorGuardianTM is a microprocessor based overload relay designed to provide protection for 3-Phase AC motors. It offers a broad range of features in one compact package providing a cost effective solution for monitoring and managing motor performance. Actual motor operating conditions are accessed by the scrolling menu and viewed by a two line highly visible vacuum fluorescent display. Fault conditions are also displayed indicating the specific cause of the occurring fault.
MPA Series specifications RELAY ACCURACY PROGRAMMABLE TRIP/ALARM POINT (Each setpoint can be disabled) Voltage Current G.F.
MGR-1000 Series The MGR Remote Manager is a component of the MotorGuardian family that is used in conjunction with the Motor Performance Analyzer (MPA ). It provides full control and monitoring of the MPA functions by mimicking the keypad and display. The front panel programming is identical to the MPA that simplifies the learning process. This external control provides an efficient and safe tool away from potentially dangerous voltages.
PRA Series The PRA-100 Series Phase Sequence Monitors are designed to allow the output to energize only when the phase connections are in the proper sequence. For use in applications where motor direction is critical or the installation is required by code to have sequence detection. When the phase sequence is correct and the operating voltage is present on all phases, the relay will energize and the green LED indicator will glow.
With normal operating voltages applied in the proper ABC sequence, the internal relay will energize (PICK-UP). When incorrect phase sequence or phase loss occurs or the three-phase voltages fall below the drop out voltages, the relay will de-energize (DROP-OUT). On models featuring indicators, the LED glows when all line conditions are normal. SLA Series The ATC Diversified SLA Series is designed to protect 3-phase equipment against PHASE LOSS, UNDER VOLTAGE, and PHASE REVERSAL conditions.
SLA Series DIMENSIONS (INCHES) PHASE VOLTAGE MONITORS STYLE "A" STYLE "E" STYLE "N" STYLE "A" wiring STYLE "b" STYLE "A" Figure 1 RB-08 or OT-08 Figure 2 RB-11 2.375" 1.75" Style B STYLE "E" STYLE "E" Figure 4 STYLE "n" 148 Figure 3 70-463-1 STYLE "n" Diversified Electronics 800.727.5646 atcdiversified.
STYLE A PLUG-IN OPERATING VOLTAGE SLA-120-ALA SLA-120-ASA 95-130 Adj SLA-230-ALA SUA-120-ALA SUA-120-ALAU* SUA-230-ALA SUA-230-ALAU* SUA-380-ASA SUA-440-ASA AGENCY APPROVAL Screwdriver — 79-108 85-117 — Lock Shaft 190-270 Adj. SLA-230-ASB SLA-380-ASA SLA-440-ASA DROP-OUT VOLTAGE 1 Ø LOW 3 Ø LOW Lock Shaft SLA-120-ASB SLA-230-ASA TYPE OF ADJUSTMENT 158-224 171-243 — Screwdriver 350-440 Adj. 430-480 Adj. 290-365 378-461 315-396 410-500 95-130 Adj. 79-108 85-117 Lock Shaft 190-270 Adj.
PBC Series The PBC Series offers protection to three-phase equipment that is required to operate between two voltage limits. All three phases are monitored individually for a pre-selected under and over voltage limit. operation With normal operating voltages applied, the internal relay will energize (PICK-UP). When the voltages on any or all phases fall outside the preset Over/Under trip points for longer than the Release delay, the relay will de-energize (DROP-OUT).
PBD Series The PBD Series offers protection to three-phase sequence sensitive equipment that is required to operate between two voltage limits. All three phases are monitored individually for a pre-selected Under and Over voltage limit, with adjustable release delay. operation With normal operating voltages applied in the proper ABC sequence, the internal relay will energize (PICK-UP).
PBE Series In today’s industrial environment, Line Noise and Power Line Harmonics are becoming an increasing problem. True-RMS detection may be necessary for achieving accurate Line Voltage measurement. operation With normal operating voltages applied in the proper ABC sequence, the internal relay will energize (PICK-UP). When the voltages on any or all phases fall outside the preset Over/Under trip points for longer than the Drop-Out Time delay, the relay will de-energize (DROP-OUT).
SLB Series The SLB Series is designed to protect three-phase equipment against Phase Unbalance, Phase Loss, and Phase Reversal conditions. operation With normal operating voltages in the proper ABC sequence and the 120 VAC control voltage applied, the internal relay will energize (PICK-UP). When any combination of Phase Unbalance exceeding the preset value or Phase Loss or Phase Reversal occurs for longer than the preset drop out time, the output relay will de-energize (DROP-OUT).
SLC Series The SLC Series is designed to protect 3-phase equipment against Phase Unbalance and Phase Loss conditions. operation With normal operating voltages applied to all three phases, the internal relay will remain de-energized (DROPPED-OUT). When a Phase Loss or Phase Unbalance exceeding the pre-selected trip point occurs, the relay will energize (PICK-UP). The SLC series is typically used in conjunction with a shunt trip breaker. Both Delta and Wye systems may be monitored.
SLD Series The SLD Series is designed to protect 3-phase equipment against Phase Unbalance, Phase Loss, Under Voltage and Phase Reversal conditions. operation With normal operating voltage present on all three phases in the proper phase sequence, the internal relay will energize (PICK-UP). When an incorrect phase sequence or phase loss occurs or the three-phase line voltages fall outside the preset unbalance or under voltage settings, the internal relay will de-energize (DROP-OUT).
SLE Series The SLE Series is designed to protect 3-phase equipment against Phase Unbalance, Phase Loss, and Under Voltage. operation With normal operating voltage present on all three phases, the internal relay will energize (PICK-UP). When a phase loss occurs or the voltages fall outside the preset unbalance or under voltage settings, the internal relay will de-energize (DROP-OUT). The relay automatically resets when the line conditions return to normal. Both Delta and Wye systems may be monitored.
SLH Series The SLH Series is designed to protect equipment against PHASE LOSS (single phasing), UNDER VOLTAGE (brown outs), and PHASE REVERSAL (improper sequence). operation When correct phase sequence and line voltage are present, the internal relay of the SLH will energize (PICK UP). When there is a phase loss, under voltage or phase reversal condition, the internal relay will deenergize (DROP-OUT). When conditions return to normal, the SLH will automatically reset. IND. CONT. EQ.
SLJ Series The SLJ Series has a built-in Delay-on-Make Time Delay. The SLJ continuously monitors the three phase lines for adverse conditions such as PHASE LOSS (single phasing), UNDER VOLTAGE (brown outs), and PHASE REVERSAL (improper sequence). When any of these conditions occur, the internal relay will de-energize (DROP-OUT). When the fault is corrected, the field adjustable Delay-on Make delay begins. Upon completion of the time delay, the internal relay will energize (PICK-UP).
• Automatic or Manual Reset PROTECTS 3-PHASE EQUIPMENT AGAINST: • Delay-on-Make Timer • Under Voltage • LED Indicators for Fault Conditions • Over Voltage • Last Fault Memory • Phase Reversal SCREWDRIVER ADJUSTMENT FOR: • Phase Unbalance • Time Delay • Phase Shift • Voltage • Frequency Shift • Phase Loss • Mode of Operation IND. CONT. EQ.
UOA Series The UOA Series offers protection to single phase equipment that is required to operate above a certain voltage minimum. OPERATION STYLE "a" Style A only STYLE "N" With operating voltage applied above the preset PICK-UP voltage, the internal relay will energize. When the voltage falls below the preset DROP-OUT voltage for a period longer than the release delay, the output relay will de-energize.
VBA Series The VBA Series offers protection to single phase equipment that is required to operate between two voltage limits. Supply voltage is monitored for a preselected UNDER and OVER voltage limit. OPERATION With normal operating voltage applied, the internal relay will energize (PICK-UP). When the voltage falls outside the preset Over/Under trip points for longer than the release delay, the relay will de-energize (DROP-OUT).
Applications PHASE VOLTAGE MONITORS APPLICATION NOTES – WIRING DIAGRAMS 162 Diversified Electronics 800.727.5646 atcdiversified.
Applications APPLICATION NOTES – WIRING DIAGRAMS PHASE VOLTAGE MONITORS SLA-XXX-AFN Diversified Electronics 800.727.5646 atcdiversified.
TYPICAL APPLICATIONS ATC-Diversified Electronics has a Current Monitor available to fit almost any monitoring application. The operation of the CM Series, AC Current Monitor/Relays, is based on an internal current transformer magnetically coupling the solid state sensing circuitry to the line being monitored.
CBA Series The CBA Series is used to detect UNDER and OVER CURRENT conditions. When the monitored current is within the normal current band, both internal relays are de-energized (Drop-out). When the current rises above the over current setting for longer than 1.0 second, the over current relay energizes (Pick-up). If the current falls below the under current setting for longer than 1.0 second, the under current relay energizes.
CDD Series The CDD Series may be used as an Over Current Monitor or an Under Current Monitor. The CDD has adjustable Delay-on-Operate and adjustable Delay-on-Release time delays. When the current exceeds the preset current trip point for longer than the Delay-onOperate time delay, the internal relay will energize (Pick-up). When the current drops below the preset current trip point for longer than the Delay-on-Release time delay, the internal relay will de-energize (Dropout).
CDO Series The CDO Series is used to detect over current conditions. The internal relay energizes (Pick-up) when the monitored current exceeds the preset trip point for longer than the adjustable time delay. The delay is incorporated to prevent nuisance tripping caused by inrush currents. The CDO has an automatic reset feature. The internal relay de-energizes (Drop-out) when the current drops 5% below the preset trip for longer than 0.2 seconds.
CDU Series OPERATION The CDU Series is used to detect Under Current conditions. The internal relay is energized (Pick-up) when the monitored current is above the preset trip point. The relay de-energizes (Drop-out) when the current falls below the trip point for longer than the adjustable delay. The delay is incorporated to prevent nuisance tripping caused by momentary line dips. The relay re-energizes when the current rises 5% above the Drop-out trip point for longer than 0.2 seconds.
CLB Series OPERATION The CLB Series is designed to protect three phase equipment against Current Unbalance and Over Current conditions. The control voltage is continuously applied to supply the sensing circuitry and the internal relay. When the current of any phase approximately 20% above the maximum operating current, the inrush delay begins. This delay disables the over current sensors while high inrush currents are present.
CMB Series OPERATION The CMB Series relay is used to detect the presence of AC current. When the monitored current exceeds the trip point for longer than 30 milliseconds, the internal relay energizes. When the monitored current drops below the trip point for longer than 0.5 seconds, the internal relay de-energizes. The Delay-on-Release is incorporated to prevent nuisance tripping caused by momentary dips in the load line. An External CT may be used to extend the range of the Current Monitor.
CMC Series The CMC Series is used to detect a motor jam up and give the equipment an opportunity to clear itself before going into a lockout and alarm mode. OPERATION Control voltage is continuously applied to the CMC monitor. Upon application of the control voltage the Forward and Alarm Relays energize. When AC current is initially applied, the Inrush Time Delay is initiated to disable the over current sensor during the inrush period. (See 1 on graph).
CMD Series OPERATION The CMD Series may be used as an Over Current Monitor or an Under Current Monitor. The CMD has adjustable Delay-on-Operate and adjustable Delay-onRelease time delays. When the current exceeds the preset current trip point for longer than the Delay-on-Operate time delay, the internal relay will energize (Pick-up). When the current drops below the preset current trip point for longer than the Delay-on-Release time delay, the internal relay will de-energize (Drop-out).
CMG Series OPERATION The CMG Series is a self powered Current Monitor/Relay that is used to detect the presence of AC current. When the monitored current exceeds the trip point for longer than 400 mSec., the internal relay energizes (Pick-up). When the monitored current drops below the trip point for longer than 50 mSec., the internal relay de-energizes (Drop-out).
CMG-0101 Series OPERATION The CMG-0101 Series is a solid state self powered Current Monitor that is used to detect the presence of AC current. When the monitored current exceeds the trip point for longer than 400 mSec., the output energizes (Pick-up). When the monitored current drops below the trip point for longer than 400 mSec., the output de-energizes (Dropout).
CMI Series OPERATION The CMI Series AC Over Current Monitor Relay operates in the failsafe model as the relay is energized (pick-up) when the monitored AC current is normal. The relay de-energizes (Drop-out) when the monitored current rises above the preset trip point or the control voltage is removed. When current is initially applied, a time delay begins. This inhibits the over current sensors while high inrush currents are present.
CML Series OPERATION The CML Series is used to detect over current conditions. The internal relay energizes (Pick-up) when the monitored current exceeds the preset trip point for longer than the adjustable time delay period. The adjustable delay is incorporated to prevent nuisance tripping caused by motor inrush currents. The CML has the manual reset feature. The internal relay de-energizes (Drop-out) when the reset button is pressed.
CMO Series OPERATION The CMO Series is used to detect over current conditions. The internal relay energizes (Pick-up) when the monitored current exceeds the preset trip point for longer than the adjustable time delay. The delay is incorporated to prevent nuisance tripping caused by motor inrush currents. The CMO has an automatic reset feature. The internal relay deenergizes (Dropout) when the current drops 5% below the preset trip for longer than 0.2 seconds.
CMU Series OPERATION The CMU Series is used to detect under current conditions. The internal relay is energized (Pick-up) when the monitored current is above the preset trip point. The relay de-energizes (Drop-out) when the current falls below the trip point for longer than the adjustable delay. The delay is incorporated to prevent nuisance tripping caused by momentary line dips. The relay re-energizes when the current rises 5% above the Drop-out trip point for longer than 0.1 seconds.
CT Series OPERATION The CT Current Transformers are of the inserted primary type with the secondary toroidally wound over a core of oriented electrical steel. The windings are carefully insulated. The entire transformer is then dipped in PVC insulation compound which insures maximum protection against moisture, acids, alkaline, oils and abrasive particles.
THREE PHASE CURRENT UNBALANCE Balanced or matched currents on a three phase system are difficult to maintain because of the many varying factors involved such as, unequal single phase loading, poor connections and cabling and/or dirty or burnt starter contacts. Example: 1. Measure the current on each leg.
ALTERNATING CONTROLLERS ATC-Diversified Electronics offers a wide variety of models for various staging requirements. The different models available are: Duplexors, Triplexors, Quadraplexors, Special Function, and Expandable Alternating Relays. The Alternating Relay is used in multiple load installations to assure equal run time on all loads. They also allow for the addition of more capacity in the event of excess load requirements.
ARA, ARB Series The Duplexor is used in control panels where two loads are required to alternate to provide equal run time on the loads. The alternating action is initiated by a control switch, which is common with one side of the control voltage. The output contacts will change states each time the control switch is opened, thus alternating the two loads. The LED indicators show the position of the output relay. The ARA Series is the standard Duplexor providing automatic alternating sequence.
ARA Series The Triplexor and Quadraplexor Alternating Relays are designed for use in multiple load installations that are required to alternate in sequence while assuring equal run time on all loads. They also allow for additional loads to run in the event of excess load requirements. The Triplexor and Quadraplexor have the option of automatic alterations or external clocking alterations.
ARA Series The Expandable Alternating Relays are designed for use in multiple load installations that are required to alternate in sequence and have the ability to accept an additional load installation in the future. ARA-120-AME: The ARA-120-AME is a Duplexor/Triplexor Alternating Relay. With the selector switch in position A, this alternating relay will duplex the loads on terminals 7 and 9. With the switch in position B, the Alternating Relay will triplex the three loads on terminals 7, 9 and 11.
ARA Series OPERATION The ARA-120-AHE is a special function Triplexor designed for three load installations. This model has a field selection switch that is used to omit one of the three loads for general or emergency maintenance while duplexing the remaining two loads. The ARA-120-AHE has the option of alternating on each load cycle or by external clocking. This alternating relay also allows for additional loads to run in the event of excess load requirements.
ARA Series OPERATION The ARA-120-AJE is a special function Triplexor designed for three load installations. This model has a field selection switch that is used to lock the Alternating Relay into a desired sequence. The ARA-120-AJE has the option of automatically alternating on each load cycle or by external clocking. This Alternating Relay also allows for additional loads to run in the event of excess load requirements.
TWO PUMP SEQUENCING: Evenly distributes run time by automatically alternating lead and lag load designations when the off control switch input opens. ARM Series Process Control Equipment for Hazardous Locations 7M26 UL913 INCLUDES INTRINSICALLY SAFE INPUTS UL913 INTRINSICALLY SAFE: Control switch inputs are low voltage/ low current and are electronically isolated from the control voltage and load alarm contacts. H-O-A Switches: Hand-Off-Automatic switches allow for manual operation.
ARM Series OPERATION DIMENSIONS (INCHES) FOUR CONTROL SWITCHING: Do not remove factory-installed jumper between terminals 2 and 3. The control switches connected to terminals 3 through 6 are labeled OFF (CS2), LEAD (CS3), LAG (CS4) and ALARM (CS5). Under normal operation the lead load energizes when the off and lead control switches close in order. The lag load energizes when the lag closes and the alarm load energizes when the alarm switch closes.
ARM Series These Triplex and Quadraplex Controllers are available with either Sequence-On-Simultaneous-Off (SOSO) or First-On-First-Off (FOFO) output logic. The special function models are differentiated by a rotary switch that allows any output to be locked as the lead load or any Process one load to be omitted while sequencing only the remaining loads.
ARM Series OPERATION triplex controllers Intrinsically safe equipment and wiring is equipment and wiring which is incapable of releasing sufficient electrical or thermal energy under normal or abnormal conditions to cause ignition of a specific hazardous atmospheric mixture in its most ignitable concentration.
The ARM-120-AGE and ARM-120-AHE Quadraplex Controllers have five switch inputs and four load outputs. The inputs are designated off, lead, lag, 2nd lag, and 3rd lag. With the off switch closed, the loads energize in sequence upon closure of the lead, lag, 2nd lag, and 3rd lag inputs. If the off switch fails to close, the lead load will not energize until both the lead and lag switches close. De-energization of the loads depends on the output logic of the selected controller.
ARM Series soso operation fofo operation STEP 1 OFF STEP 1 This example illustrates the normal operation of the Triplex Controller in a 2ND pump down application with four normally LAG open dry float switches. The switches are LAG designated off, lead, lag, and 2nd lag. The example begins with all switches open and LEAD all loads de-energized. STEP 2 This example continues from SOSO operation step four. With all float switches 2ND closed, all loads are energized.
Class and group specify the type of hazardous substance that may exist in the classified location. The division indicates the conditions under which the hazardous substance may be present. CLASS I Locations in which flammable gases or vapors may be present in the air in quantities sufficient to produce explosive or ignitable mixtures. CLASS II Locations which are hazardous because of the presence of combustible dust. GROUP A Atmospheres containing acetylene.
ISO Series OPERATION The ISO Series single channel devices are used to provide a safe and reliable means of controlling loads from hazardous locations without releasing sufficient energy, under normal or abnormal conditions, to cause ignition of a flammable or combustible atmospheric mixture while in its most easily ignited concentration. An isolated output turns on when the control switch input from the hazardous location is closed. When the control switch input opens, the isolated output turns off.
The ISO/ISL Series multiple channel devices are used to provide a safe and reliable means of controlling loads from hazardous locations without releasing sufficient energy under normal or abnormal conditions to cause ignition of a flammable or combustible atmospheric mixture while in its most easily ignited concentration. An isolated output turns on when the corresponding control switch input from the hazardous location is activated.
ISO, ISL Series ISOLATED SWITCHES 196 Diversified Electronics 800.727.5646 atcdiversified.
AC Series The AC 2020 Compressor Protector provides multimode time delays, reset selections and a memory capability which indicates using LED’s, the last fault condition. This offers not only protection for the compressor in adverse electrical conditions but also a method to readily determine the type of fault occurrence. operating voltage Auto Ranges 190-270 VAC, Adj., 50/60 Hz 380-540 VAC, Adj.
AC-503 Series This family of HVAC controls provides short cycle protection by locking out the compressor for a period of time after a voltage or thermostat interruption. Subsequent interruptions will not increase the delay period. Since the delay begins when the interruption occurs, the temperature control is not affected. Under normal operating conditions, the compressor off time is longer than five (5) minutes. In this case, the use of these timers will not lengthen this off cycle.
AC-505-5 The AC-505-5 provides short cycle protection by locking out the compressor for a period of time after a voltage or thermostat interruption. Subsequent interruptions will not increase the delay period. Since the delay begins when the interruption occurs, the temperature control is not affected. Under normal operating conditions, the compressor off time is longer than five (5) minutes. In this case, the use of these timers will not lengthen this off cycle.
ASC-500 This family of controls provides short cycle protection by locking out the compressor for a period of time after a voltage or thermostat interruption. Subsequent interruptions will not increase the delay period. Since the delay begins when the interruption occurs, the temperature control is not affected. Under normal operating conditions, the compressor off time is longer than five (5) minutes. In this case, the use of these timers will not lengthen this off cycle.
AC-800 Series The ATC Diversified STAR PERFORMER provides short cycle protection of compressors by delaying restart after a voltage or control circuit interruption. When the interruption occurs, the control relay drops out. The delay period begins when power is restored, providing random restart. This universal voltage Delay-on-Make Short Cycle Timer provides the ultimate protection against short cycling of a compressor.
ASC-600 Series The ASC-600 Series provides short cycle protection of compressors by delaying restart after a voltage or control circuit interruption. When the interruption occurs, the control relay drops out. The delay period begins when power is restored, providing random restart. These are easy to install, two (2) terminal short cycle timers that connect in series with the control voltage and control relay.
AC-410 Series The AC-410 Series are plug in Phase Sequence and Loss Monitors that protect 3 phase refrigeration equipment from adverse line conditions such as: PHASE LOSS (SINGLE PHASING): When any one phase drops to 83% or less of the adjustment setting. UNDER VOLTAGE (BROWN OUTS): When all three phase voltages drop to 90% or less of the adjustment setting. PHASE REVERSAL (IMPROPER SEQUENCE): When the wrong sequence is applied to the equipment.
CV Series CV-100RS 1.5" X 2.65" X 3.75"H OPERATION This switch should be positioned to match the line voltage for proper operation. When the line voltage goes below (brown out) or above the preselected operating range, the internal relay drops out removing the plugged-in appliance from these adverse fault conditions. When the voltage returns to the normal operating range, a five (5) minute delay begins. Upon completion, the internal relay picks up allowing the plugged-in appliance to start.
SPM Series OPERATION The ATC Diversified SPM Series Single Channel Seal Failure module is a specialized control for monitoring the shaft seal of a submersible pump motor. A leak is detected by sensing the position of a resistive float switch installed in the seal cavity. When the resistance drops below the sensitivity rating, the output relay energizes and the LED illuminates.
SPM Series OPERATION The ATC Diversified Electronics SPM Series Seal Failure module is a specialized control for monitoring the shaft seals of submersible pump motors. Leaks are detected by sensing the conductivity of the contaminating fluid through probes installed in the seal cavity. When a seal begins to leak, the seal failure module energizes one of its SPST output relays indicating that the seal needs to be replaced before the motor is damaged. The sensitivity of the probe inputs is field adjustable.
SPM Series OPERATION The non-volatile Latching Temperature Switch relay monitors a normally-closed-low temperature switch. It incorporates a bistable relay that retains its state during power failures. LEDs indicate the status of the relay, and connections for an external reset button are provided for manual control. The reset inputs of multiple units may be connected to a single push button as long as proper polarity is observed when making the connections.
SPM Series The ATC Diversified Submersible Pump Monitor is a specialized control for monitoring the shaft seal and stator temperature of a submersible pump motor. Seal leakage is detected by either a resistive float switch or a pair of conductive probes installed in the seal cavity. Over-temperature is detected by a normally-closed-low temperature switch mounted on the stator. The over-temperature function incorporates a bistable relay that retains its position during power failures. IND. CONT. EQ.
WIRING Figure 1 shows the connections for use with a Flygt model FLS float switch. The leakage sensitivity must be adjusted to 1 k for float switch applications. If a pair of conductive probes is used to sense seal leakage, a 100 k resistor is required as shown in Figure 2, and the sensitivity should be set to the desired value. SPM Series OPERATION SPECIAL CONTROLS The states of the unit’s relay outputs are determined by the series combination resistance of the leakage and temperature sensors.
PRT Series The PRT-100 is a hand-held tester that takes the guesswork out of connecting a 3-phase motor. The direction of rotation of a motor depends on phase sequence of the power line connections. If the sequence is reversed, the motor will run in the wrong direction, possibly damaging the equipment connected to the motor. The PRT-100 identifies the leads of a three-phase motor and detects the sequence of a three-phase power line.
UPA-100 Series The UPA-100 Power Alert reduces the risk of electrical arc flash by pre-verifying the electrical isolation from outside of a control panel. Hard wired to the circuit breaker or main disconnect, the UPA flashes whenever voltage is present. Engineered with redundant circuitry, the Power Alert is powered by the same voltage that it indicates. IND. CONT. EQ.
UPA-130 Series The UPA 130 Power Alert reduces the risk of electrical arc flash by pre-verifying the electrical isolation from outside of a control panel. Hard wired to the circuit breaker or main disconnect, the UPA flashes whenever voltage is present. Engineered with redundant circuitry, the Power Alert is powered by the same voltage that it indicates.
POWER ALERTS UPA-130 Series WIRING DIMENSIONS (INCHES) _ _ + _ + _ Diversified Electronics 800.727.5646 atcdiversified.
UPA-200 Series The UPA-200 Power Alert reduces the risk of electrical arc flash by pre-verifying the electrical isolation from outside of an electrical panel. Hard wired to the circuit breaker or main disconnect, the UPA LED's flash to indicate the presence of hazardous conditions (20-600 VAC & 20-1000 VDC) associated with stored energy. Engineered with redundant circuitry, the power alert is powered by the same voltage that it indicates.
L1 WIRING FUSED SAFETY SW. OR BREAKER N G L1 L2 L3 GND FIBER OPTIC CABLE 3-PHASE WYE 4W + GND MAIN FEED N GRN/YEL EARTH FIBER OPTIC CABLE L1 L2 UNGROUNDED OR HIGH RESISTANCE GROUND WYE N G L1 L2 L3 GND GRN/YEL L1 L2 L3 GND CABLE GRN/YEL With or without DC- grounded MAIN FEED L1 L2 L3 GND FIBER OPTIC CABLE FUSED SAFETY SW. OR BREAKER EARTH L1 N G EARTH GRN/YEL GRN/YEL EARTH L1 FUSED SAFETY SW.
BFA Series OPERATION With nominal 3-phase line voltage applied, a flashing green NORMAL LED gives positive indication of a good fuse and integrity of the wire connection to each side of the fuse.1 A flashing red FAULT LED gives positive indication of an unconnected or open fuse, or a BFA wiring fault that needs corrected such as a lost connection to either side of the fuse or mismatched line and load wires.2 When phase loss occurs, both FAULT and NORMAL LEDS will extinguish.
A. Normal, fuse good, electrical contact across fuse 2. A. Unconnected or blown fuse B. Bad Connection Load Side (white stripe wire) C. Both of the above A. Phase voltage loss with no motor regeneration B. The above accompanied with an unconnected or blown fuse A. Bad Connection Line Side (solid color wire) B. The above accompanied with an unconnected or blown fuse C. Phase Voltage loss with motor regeneration accompanied with an unconnected or blown fuse A.
GFD Series The ATC Diversified Electronics GFD Series is intended for the use on ungrounded systems to detect and indicate the phase of the first ground fault condition. This enables corrective action to avoid the potential hazards resulting from a second ground fault. OPERATION With nominal 3 phase line voltage applied, a flashing NORMAL green LED gives indication of a non-fault condition and integrity of the wire connection to the corresponding phase.
Sockets RELAY SOCKETS SURFACE MOUNTED— RB-08 Recommended for use with all 8 pin octal plug-in devices. UL Recognized and CSA Certified for 10 Amps @ 600 VAC. The molded thermoplastic base has brass, nickel plated inserts with #6-32 steel, nickel plated screws. SURFACE MOUNTED— RB-11 Recommended for use with all 11-pin magnal plug-in devices. UL Recognized and CSA certified for 10 Amp @ 300 VAC. The molded thermoplastic base has brass, nickel plated inserts with #6-32 steel, nickel plated screws.
Sockets & Accessories ACCESSORIES ADJUSTMENT—101026105 Recommended for use with all the ATC Diversified Electronics family of “remote adjustable” timers. Proper spacing is maintained for UL and CSA applications. This linear taper potentiometer has a non-conductive shaft attached to the internal conductive plastic wafer.