Owner`s manual

Page 4
B-Series DV-2 Gas Fireplace
Part No. XG0160 - 080410
Installation
Installing and Framing the Fireplace
The B-Series-DV-2 replaces may be installed in any location that main-
tains proper clearances to air conditioning ducts, electrical wiring and
plumbing. Safety, as well as efciency of operation, must be considered
when selecting the replace location. Try to select a location that does
not interfere with room trafc, has adequate ventilation, and offers an
accessible pathway for Direct Vent installation. Refer to page 4 - Vent
Installation for more information.
The replace dimensions are shown below:
Figure 3. Minimum Corner framing dimensions, using a 45° elbow.
Figure 2. Framing dimensions.
* When sheetrock is
not used behind the
fireplace, framing
depth may be reduced
by 5/8"
Framing
Top View
Front View Side View
Clearances
These clearances apply to all dimensions except the framed opening,
where the clearance to combustibles is 0". The B-Series DV-2 clearances
to combustible materials are:
B34-DV-2 B38-DV-2
Top - Rear Vent * 7 1/2" 7 1/2"
Top - Top Vent 17 1/2" 17 1/2"
Back 1" 1"
Sides 1" 0"
Floor 0" 0"
Mantle** 8" 6"
* Clearance from the top of the replace to a combustible ceiling
within the replace enclosure.
** Refer to page 12, (Mantels and Surrounds).
Unprotected combustible walls which are perpendicular to the replace
opening, must not project beyond the shaded area shown in Figure 25.
For protection against freezing temperatures, it is recommended that
outer walls of the chase be insulated with a vapor barrier. This will reduce
the possibility of a cold-air convection current on the replace.
Figure 1. Fireplace dimensions.
M
N
O
N
P
Q
2" clearance
to corners only
M
N
O
N
P
Q
2" clearance
to corners only
M
N
O
N
P
Q
2" clearance
to corners only
A B C D E F G H I J K L
B34-DV-2 33
3
/
4 31
1
/
2 31
1
/
4 1
1
/
4 18 1 13
3
/
4 21
3
/
4 8 4 7 25
1
/
4
B38-DV-2 37
3
/
4 34
1
/
2 34
3
/
4 1
1
/
4 21 1 15
7
/
8 24
1
/
8 9 4 7 28
3
/
8
M
N
O
N
P
Q
2" clearance
to corners only
M
N
O
N
P
Q
2" clearance
to corners only
M N O P Q S T
B34-DV-2 36
3
/
4 33 15
1
/
2 50 35
3
/
8 30
3
/
8 39
7
/
8
B38-DV-2 39
3
/
4 37 17
5
/
8 56 39
5
/
8 33
3
/
8 42
7
/
8
When installing a shelf over the top of the replace, the following
guidelines must be adhered to: For Rear Vent applications the
minimum clearance from the top of the replace to a shelf is 7 1/2". For
Top Vent applications, the minimum clearance is 17 1/2". (Minimum
2" clearance must still be maintained around the vent pipes.)
Figure 1a. Framing for shelves over the fireplace.
(Dimension "L" refer Figure 1 Fireplace Dimensions.)
Top Vent
Rear Vent
(On Applicable Models)
M
7 1/2
S
Header
Shelf
L
T
17 1/2
Header
MEL Short
Shelf
M
2” Min
WARNING!
When this appliance is installed directly on any combustible mate-
rial other than wood ooring, it must be installed on a metal or
wood panel extending the full width and depth of the appliance.