Installation guide

Page 7
Part No. XG0509
DFSP Rio Pedestal Stove
Quality Gas Products by Montigo
Installation
Direct Vent
Top Vent Venting Runs
For the Rio Pedestal Stove there are two types of Top Vent (DV)
installations: A) Horizontal (Through-The-Wall) Installations and B)
Vertical (Through-The-Roof) Installations.
Allowable Vent Runs
Before you install any venting, you must determine whether the
venting run will be acceptable. Unacceptable venting can affect the
fireplace's combustion. Figure 12 shows various vent rises and the
corresponding number of 90° bends which can be made.
A) Through-the-Wall (Horizontal) Venting Option
The horizontal venting option requires an FSTK02 Vent Kit. Figure 13
shows the components which are used to attain different vent heights.
Additional stove pipe or Montigo Standard Series vent components
may be used to increase the vent run, as long as the run still falls
within the limits set out in Figure 12.
1
- Vertical Rise is measured
from the center of the stove's
flue collar to the center of the
termination.
2
- A - Top Vent Conversion Box
(FST04)
B - Std. Stove Pipe (FST11)
C - 90° Elbow (MEL9MB)
D - Oversize Stove Pipe
(FST05)
E - Standard Termination
(MTO-3)
Installing the Stove Pipe
1. Ensure that the intended pathway for the venting is clear.Try to
position the stove midway between two studs to avoid having to
cut them. Cut and frame a 10" x 10" hole for the termination.
2. Attach the top vent conversion box (Part # FST04) to the stove's
flue collar as shown in Figure 14. Secure it with four sheet metal
screws.
Stove pipe
sections
Figure 14. Attaching the top vent conversion box. Installing the
stove pipe.
3. Cut the flex pipe (Part # FST08) to length and install the second
flex collar. Install the flex liner onto the inner collar of the conver-
sion box.
Figure 13. Possible venting configurations using the FSTK02 kit.
Figure 12. Venting limitations for top vent installations.
Vertical Rise 24 - 34"
Vertical Rise 33 - 56"
Vertical Rise 55 - 77"
H2
V
H1
B
B
BB
E
E
E
B
B
B
B
D
D
C
C
C
A
The minimum vertical rise for a Top Vent Installation is 2', which al-
lows 1 - 90° elbow and a maximum horizontal run of 10'. With greater
vertical rise, the number of 90° bends may be increased according to
the chart below. The total maximum horizontal run (H
T
) is also shown,
and the run between each elbow (H
x
) may be any length, as long as it
does not exceed (H
T
).
Vent Rise
1
Max. # Max. Horiz.
(V) of elbows Run (H
T
)
2' (min.) 1 10'
4' 2 10'
5' 2 10'
10' 3 10'
15' 3 10'
20' 3 10'
25' (max.)
See vertical vent section
1
Vertical rise is measured from the center of the stove's flue
collar to the center of the termination.
2
See 'Through-the-Roof Installations'
Example:
If V= 12', the vent run may use up to 3 - 90° elbows.
If H
1
= 3', H
2
=2', and H
3
=3',
then H
T
=8'.
This would be an acceptable installation.
FST04
Conversion box
4” Inner Elbow