Owner`s manual

Page 6
H-Series DL Gas Fireplace
Part No. XG0140 - 092210
Section 2: Framing
Installation
1). Frame in the enclosure for the unit with framing materials. The
framed opening for the assembled replaces are as shown below,
see Figure 2
.
NOTE: When constructing the framed opening, please ensure
there is access to install the gas line when the unit is installed.
See Figure 22.
Clearances
When installing a shelf over the top of the replaces, the following
guidelines must be adhered to:
For Rear Vent applications, the minimum clearance is 2" from the rear
of the replace to a wall, or any combustible materials, and 9" clearance
from the top of the replace to the underside of any combutible shelf
materials.
For Top Vent applications, the minimum clearance is 2" from the rear of
the replace to a wall, or any combustible materials, and 17 1/2" to the
underside of any combustible shelf materials, Figure 4.
For Top or Rear Vent applications where the Minimum mantel height
is required above the replace, (for an alcove or low prole shelf), ALL
Materials MUST BE NON-COMBUSTIBLE, Figure 5. The minimum
clearance is 2" from the rear of the replace to a wall, or any combustible
materials.
The replace clearances are shown below:
* When sheetrock is not used behind
the replace, framing depth "O" may be
reduced by 5/8".
0" clearance
to corners only
P”
N”
Q”
N”
M”
O”
Figure 2. Framing dimensions, (Straight wall & Corner Installation).
(ALL Models, shown in Table on Page 3).
Figure 4. Combustible Framing for shelves over the replace, Top
vent.
Figure 3. Combustible Framing for shelves over the replace, Rear
vent.
H*DL* 9 17 1/2 2 1 0 4
MODEL
Top -
Rear Vent*
Top -
Top Vent
Back
Sides
Floor
Mantel
M N O P Q S T
H34DL*
37 1/4 33 3/4 17 7/8 52 3/8 37 31 41
H38DL*
40 1/4 37 3/4 18 7/8 57 1/2 40 5/8 34 44
H42DL*
44 1/4 42 19 3/8 63 3/4 45 1/8 38 48
Installing The Standoffs
To avoid elevated mantel temperatures, all H*DL*- Series gas
replaces are required to have the supplied standoffs installed.
The replace is supplied with two standoffs. Bend and install these
standoffs on top of the replace ensuring that the height of the standoff
maintains a MIN. 6" clearance.
Figure 6. Installing the standoff's.
M
9”
S
L
18”
max.
2”
min.
Combustible
Header
Combustible
Shelf
Exterior
Wall
L
PEL Shor t
90° elbow
M
17 1/2”
2” min.
Combustible
Header
Combustible
Shelf
Exterior
Wall
"L" Dimension, see
table on Page 5.
*
Dimension for Top
vent replaces, see
graphs, gures 14,
15 & 16.
*
6"