Owner`s manual

Page 13
H*38DF-PFC* Indoor Gas Fireplace
Part No. XG0816 - 100210
48”Rigid
53” Flex
42”
33”
12”
B
C
A
Figure 17. Rear Vent Venting Graph for wall mounted terminations.
Figure 17b.
Rear Vented, wall mounted Multi-elbow termination
installation. Installation for H*38PF* must have a minimum
vertical rise of 48" with Rigid vent pipe, and 53"Min with
Flex.The vent run must comply with the Venting Graph for
Rear vent, wall mounted terminations, Figure 17.
Figure 17a. Straight run, Rear Vented, wall mounted termination for
H*38PFN*, Figure 17.
Installation
If your installation does not fall
within the venting graph para-
meters, please contact Montigo
for Power Venting options.
Notes Wall Mounted Terminations: Rear Vent
All dimension lengths for vertical or horizontal runs are measured
from center of the vent pipe.
Venting runs must fall within the limits set by the venting graphs,
see Figure 17.
Fireplace must be converted to Rear Vent conguration prior to
running vent, see Figure 7 and 8.
The Venting Graph
Measure the vertical height from the replace hearth to the centre of the
termination and the horizontal run from the replace ue collar to the wall
ange of the termination. Plot on the Venting Graph Figure 17 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 120" and the horizontal
run to the wall ange of the vent termination is 138", this would be
an acceptable installation.
Example B: (Acceptable Installation)
If the vertical dimension from the hearth is 66" and the horizontal
run to the wall ange of the vent termination is 66", this would be
an acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the oor of the replace is 72" and
the horizontal run to the wall ange of the vent termination is 120",
this would NOT be an acceptable installation.
Unacceptable vent run
within shaded area.
Acceptable vent run
within non-shaded area.
Hearth
12”
MAX.
RHS8 Heat
Shield
Termination
Exterior
Wa
ll
33”
NOTE: 12” MAX.
horizontal run with
no vertical lift.
42” Max.
53” Min. Flex
48” Min.Rigid
12”
Max.
20”Min. Flex
15”Min. Rigid
33”
Hearth
Flex or Rigid
Section