Owner`s manual
H*38DF ST Indoor Gas Fireplace
Page 12
XG0207 - 011012.1
Installation
The Venting Graph: H*38DF*-ST
Measure the vertical height from the replace hearth to the centre of the
termination and the horizontal run from the replace ue collar to the wall
ange of the termination. Plot on the Venting Graph Figure 13 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 114" and the horizontal
run to the wall ange of the vent termination is 168", this would be
an acceptable installation.
Example B: (Unacceptable Installation)
If the vertical dimension from the hearth is 36" and the horizontal
run to the wall ange of the vent termination is 84", this would
NOT be an acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the oor of the replace is 60" and
the horizontal run to the wall ange of the vent termination is 144",
this would NOT be an acceptable installation.
Figure 13. Top Vent Venting Graph for wall mounted terminations.
Figure 13a. Top Vented, wall mounted installation with one 90° bend. The vent
run must comply with Venting Graph for Top vent, wall mounted terminations,
Figure 13.
Figure 13b. Top Vented, wall mounted Multi-elbow installation. See Venting
Graph for Top vent, wall mounted terminations, Figure 13.
Section 3-3-1: VENTING LAYOUT: Wall mounted termination.
Selection of components and details of venting layout should adhere
to the following guidelines:
Vent terminations must not be recessed in walls or siding.
All through-the–wall terminations within 3’ of the replace must
have a Montigo Heat Shield (RHS101) installed. See Section
3-3-3.
All through-the-wall terminations beyond 3' of the replace must
have a Montigo Heat Shield (RHS8) installed. See Section 3-3-3.
Once the proposed venting layout has been determined refer to
Figure 13 or 14 to ensure the layout is acceptable.
Notes Wall Mounted Terminations: TOP VENT
All measurements for vertical or horizontal runs are measured
from center of the vent pipe.
Venting runs must fall within the limits set by the venting graph,
see Figure 13.
Wall mounted Terminations
The following details are some possible congurations for Wall
mounted terminations.
Solid Section
Flex Section
Hearth
30”min
15’ foot Max.
RHS8 Heat
Shield
Termination
Exterior
Wa
ll
9' min
at Max
horizontal
WARNING:
An inspection of the explosion relief appers and door
MUST be made prior to lighting the replace. A faulty seal
on the door gasket and/or explosion ports will result in
products of combustion leaking into the living space and
may result in carbon monoxide poisoning.
RHS101
42” Max
.
46”Min.
Termination
Exterior
Wall
Hearth
42
”
46”
A
C
B
Unacceptable vent run
within shaded area.
Acceptable vent run
within non-shaded area.
If your installation does not fall within
the venting graph parameters,
please contact a local Montigo dealer
for Power Venting Options.