Installation
Vent Installation
This section covers the installation of direct venting and terminations.
Installation Requirements
H42DF-Series fireplaces are certified for use with Montigo Standard Series
(5" / 8") venting components.
Minimum clearance to combustible construction around the vent pipe
is 1" on all sides, except on horizontal venting where the top of the pipe
must have a clearance of at least 2".
Use only certied Montigo vent components. (Use of other parts will void
the Montigo warranty, and may impede the operation of the fireplace.)
All joints must be secured with a minimum of two screws per joint
Vent terminations must not be recessed in walls or siding
Horizontal runs must be supported by a minimum of two supports per horizontal
run. A minimum of one screw on each side of support is also required
Flex vent sections may be stretched up to 50% of their total length (eg. a
24" section may be stretched to 36")
Solid vent sections may be cut less than half way from the female end
Venting components can be used in any combination of solid/rigid pipe or flex
pipe and in any orientation (Male connectors can face in any direction)
Vent Terminations
Selecting A Termination Location
Choosing your vent termination location will help to determine whether
youneedtouseatopventorrearventreplace.Figure6a,below,shows
typicalreplacelocationsandtheventingoptionstheyprovide.
For a more detailed diagram of allowed termination locations, see Ap-
pendix A.
Figure 6a. Fireplace locations and vent terminations.
Installing The Gas Line
The gas line must be installed before nishing the H42DF-Series
Fireplace. Natural Gas requires a minimum inlet gas supply pressure
of5.5"W.C.&amanifoldpressureof3.5"W.C.Propane Gas requires a
minimuminletgassupplypressureof11"W.C.&amanifoldpressureof
10"W.C.Provisionmustalsobemadefora1/8"N.P.T.pluggedtapping
and be accessible for test gauge connection immediately upstream of
thegassupplycontrolstotheappliance.Thereplacegasconnection
and the main operating gas valve is located behind the removable trim
at the bottom of the unit and need only be attached to the gas line with
anapprovedtting,asrequiredbytheapplicable installation codes.
To access the replace gas connection the main burner must be
removed as shown below in gure 5b.
•Onlyusegasshut-offvalvesapprovedforusebythestate,province,
region, or governing body, in which the appliance is being installed, or
as required by the applicable installation codes.
•Flexiblegasconnectorsmustnotexceed3feetinlength,unlessitis
allowable within applicable installation codes.
Note: After gas line is connected, each appliance connection,
valve and valve train must be checked while under normal
operating pressure with either a liquid solution, or leak
detection device, to locate any source of leak. Tighten any
areas where bubbling appears or leak is detected until
bubbling stops completely or leak is no longer detected.
DO NOT use a flame of any kind to test for leaks.
Figure 5a. Gas line access.
The appliance and its individual shut-off valve must be disconnected
from the gas supply piping system during any pressure testing of that
system at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system by
closing its individual manual shut-off valve during any pressure testing
of the gas supply piping system at test pressures equal to or less than
1/2 psig (3.5 kPa).
Burner Tray Gasket
Figure 5b. Gas line access.
Gasline Acces
0.875 dia.
7
to center
2
Cautions:
Vent terminations can be very hot. If the termination is less than 7 feet
above a public walkway, it should be fitted with a certified Montigo
Heat Guard. (Part no. PTKOG).
Do not obstruct, or attempt to conceal the vent termination.
These actions will affect the operation of the fireplace, and may
be hazardous.
In heavy snow areas, take extra care to prevent snow buildup
from obstructing the vent termination.
Use Montigo Vinyl Heat Shield (Part no. VSS) when using on ap-
plications with vinyl siding to guard against possible damage.