L38DF-ST* Indoor Gas Fireplace
Part No. XG0810 - 081310-1
A
B
C
42”
42”
26 3/4”
12”
Figure 17. Rear Vent Venting Graph for wall mounted terminations.
Figure 17b. Rear Vented, wall mounted Multi-elbow termination
installation. Installation for L38DF*-ST must have a minimum
vertical rise of 42".The vent run must comply with the Venting
Graph for Rear vent, wall mounted terminations, Figure
17.
Figure 17a. Straight run, Rear Vented, wall mounted termination for
L38DF-ST*, Figure 17.
Installation
If your installation does not fall
within the venting graph para-
meters, please contact Montigo
for Power Venting options.
Notes Wall Mounted Terminations: Rear Vent
All dimension lengths for vertical or horizontal runs are measured
from center of the vent pipe.
Venting runs must fall within the limits set by the venting graphs,
see Figure 17.
Fireplace must be converted to Rear Vent conguration prior to
running vent, see Figure 7 and 8.
The Venting Graph
Measure the vertical height from the replace hearth to the centre of the
termination and the horizontal run from the replace ue collar to the wall
ange of the termination. Plot on the Venting Graph Figure 17 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 120" and the horizontal
run to the wall ange of the vent termination is 138", this would be
an acceptable installation.
Example B: (Uncceptable Installation)
If the vertical dimension from the hearth is 48" and the horizontal
run to the wall ange of the vent termination is 72", this would be
would NOT be an acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the oor of the replace is 60" and
the horizontal run to the wall ange of the vent termination is 144",
this would NOT be an acceptable installation.
Unacceptable vent run
within shaded area.
Acceptable vent run
within non-shaded area.
30” Max.
42” Min.
12”
Max.
Flex or Rigid
Section
15 1/4”
Min.
26 3/4”
Hearth
26 3/4”
PXT Extension
RHS101 Heat
Shield
Termination
Hearth
Exterior
Wall
NOTE:
12” MAX. horizontal
run with no vertical lift.
12” MAX.
WARNING:
An inspection of the explosion relief appers and door
MUST be made prior to lighting the replace. A faulty
seal on the door gasket and/or explosion ports will
result in products of combustion leaking into the living
space and may result in carbon monoxide poisoning.