Owner`s manual

Page 10
L52DF-ST* Indoor Gas Fireplace
Part No. XG0811 -100511
The Venting Graph: L52DF-ST*
Measure the vertical height from the replace hearth to the centre of the
termination and the horizontal run from the replace ue collar to the wall
ange of the termination. Plot on the Venting Graph Figure 14 with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
Example A: (Unacceptable Installation)
If the vertical dimension from the hearth is 84" and the horizontal
run to the wall ange of the vent termination is 36", this would
NOT be an acceptable installation
Example B: (Acceptable Installation)
If the vertical dimension from the hearth is 108" and the horizontal
run to the wall ange of the vent termination is 120", this would be
an acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the oor of the replace is 48" and
the horizontal run to the wall ange of the vent termination is 108",
this would NOT be an acceptable installation.
Section 3-3-1: VENTING LAYOUT: Wall mounted termination.
Selection of components and details of venting layout should
adhere to the following guidelines:
Vent terminations must not be recessed in walls or siding.
All through-the–wall terminations within 3’ of the replace must
have a Montigo Heat Shield (RHS101) installed. See Section
3-3-3.
All through-the-wall terminations beyond 3' of the replace must
have a Montigo Heat Shield (RHS8) installed. See Section 3-3-3.
Once the proposed venting layout has been determined refer to
Figure 14 to ensure the layout is acceptable.
Notes Wall Mounted Terminations: Top Vent
All measurements for vertical or horizontal runs are measured
from center of the vent pipe.
Venting runs must fall within the limits set by the venting graph,
see Figure 14.
Wall mounted Terminations
The following details are some possible congurations for Wall
mounted terminations. See below.
PTKOG (5"/8")
1. Ensure that the two long mounting brackets are facing the bottom
of the termination. (See inset). This will provide more heat protection
at the top of the termination, where temperatures are highest.
2. Attach to the faceplate of the termination using four sheet metal
screws.
Figure 13c. Installing a PTO termination heat guard.
Installing Heat Guards over Terminations is recommended
in installations where the termination is located within 7' feet above
grade, or above a pedestrian walkway, and may be Required by code
in Public areas.
1. Ensure that the two long mounting brackets are facing the bottom
of the termination. (See inset). This will provide more heat protection
at the top of the termination, where temperatures are highest.
2. Attach to the faceplate of the termination using four sheet metal
screws.
Installation
WARNING:
An inspection of the explosion relief appers and door
MUST be made prior to lighting the replace. A faulty
seal on the door gasket and/or explosion ports will
result in products of combustion leaking into the living
space and may result in carbon monoxide poisoning.