Owner`s manual

Page 11
L52DF-ST* Indoor Gas Fireplace
Part No. XG0811 -100511
B
A
Horizontal Run
(
in.
)
Vertical Height (in.)
84”
126”
C
Figure 14. L52DF-ST* Top Vent Venting Graph for wall mounted
terminations.
If your installation does not fall
within the venting graph para-
meters, please contact Montigo
for Power Venting options.
Figure 16. Top Vented, wall mounted installation with 1 elbow (1 one
90° bend). The vent run must comply with Venting Graph
for Top vent, wall mounted terminations, Figure 14.
Figure 16a. Top Vented, wall mounted Multi-elbow installation. See
Venting Graph for Top vent, wall mounted terminations,
Figure 14.
Unacceptable vent run
within shaded area.
Acceptable vent run
within non-shaded area.
Figure 19c. RHS101 Installation. (Install by sliding Outer Section over vent
pipe where it passes through the combustible construction.
Figure 19d. Heat Shield. After sliding the outer section in place.
Section 3-3-3: Heat Shields
Installing a Wall Mounted RHS101 Heat shield.
The RHS101 Heat shield MUST be used with the L52DF-ST*.
To install the RHS101, Slide the Inner Section over the vent pipe that
will connect to the replace. Then fasten the vent pipe to the back of the
replace with a minimum of three sheet metal screws. (Note: ensure you
maintain the Max. 12" replace clearance). From the outside slide the
RHS101 outer section on see Figure 19c. To complete the installation
fasten the Heat Shield Outer Section & Termination frame to the structure
Figure 19d.
RHS8
84”Min
.
Combustible
framing
Termination
Drywall / sheetrock
RHS101 Heat Shield, inner Section
RHS101 Heat Shield
Outer Section
Vent pipe, from fireplace
Drywall / sheetrock
RHS101 Heat Shield, inner Section
Termination
RHS101 Heat Shield
Outer Section
Installation
RHS8
126” Max
.
84” Min.