Instruction manual

NOTE: Remember, both sides of the Fireplace require the same quantities of wood, drywall and hardware.
Cut the Upper and Lower Horizontal 2 x 4's as shown in Figure 2. Next, cut the Required quantity of short ller 2x4's under the lower Horizontal.
Follow Typical building codes and practices when spacing. Next, cut the Required Left and Right Vertical 2 x 4's as shown in Figure 3.
Lastly, install the Two (2) Supplied Steel Headers above the replace throat positioned to attach facing material.
NOTE: Whenthisassemblyisinplace,ensureALLtherequiredclearancestocombustiblesaremaintained.
Figure 3 Sec.2 Fireplace installation, Both Sides are Typical.
Step 4. Installation of the RHS 102 heat shield (See "Figure 7 Sec.4 on page 15").
When the vent passes through the rst adjacent ceiling (or wall for horizontal runs) a Montigo RHS102 heat shield must be installed around
the pipe as shown above.
See the detail of the RHS 102 on page 13.
1” clearance
1” clearance
Non-Com
b
usti
bl
e
h
ea
d
er
(supplied by Montigo)
2-pcs 2 x 4 (vertical)
Both Sides Typ
2 x 4, (Top
horizontal)
2 x 4, (Bottom
horizontal)
Both
Sides
Typ
(vertical)
use Typical
building
practices
when
spacing.
RHS 102
Note: Images are shown without screens for clarity purposes.
However, your replace should not be operated without proper
installation of screens.
R520-ST & R620-ST Power Vent Indoor Gas Fireplace
Page 10
XG0773 - 150127