C-View Residential R520-R620 Series Indoor Gas Fireplace
Part No. XG0771 - 0070111
f i r e f e a t u r e
Installation
Top View
Vertical Power Vent
Requirements
It is recommended that the External Power Vent System be used with
a gas replace that is equipped with HSI. When installing the venting,
the installation must adhere to the Vent Installation Section in the re-
place's Installation Operation and Maintenance Instructions, as well
as the following guidelines:
The EPVRR Power Vent dimensions are show below.
Front View
The Vertical EPVRR
Power Vent
Installation Requirements for Vertical Power Venter
The C-View Residential Series replace use a Designated coaxial vent
system designed specically for the Residential replace, and Use of other
non-certied parts will void the Montigo warranty, and may impede the opera-
tion of the replace.
Ensure that the planned termination location is acceptable as shown
in Appendix A.
Maximum allowed vent run is 100 feet. (Refer to Montigo Reference
Document, XG1035) for all Possible variations not described here.
Vertical runs must be supported by a minimum of three supports per 10 feet
of venting.
For vertical installations the longest vent run is 140 feet with a limit of 6
-90° Elbows, or 12 - 45° Elbows. For longer runs contact the C-View
Manufacturer.
It is important that the location of the power vent motor is not exposed to a
downfall of water not in excess of the standard rain fall.
The Vertical EPVRRF
Power Vent Rough-in Frame
Installation Requirements for Vertical Power Venter Rough-
in Frame.
The C-View Residential Series replace use a Designated coaxial vent
system designed specically for the Residential replace, and Use of other
non-certied parts will void the Montigo warranty, and may impede the opera-
tion of the replace.
Top View
Front View