DS2100 User's Manual  SECTION 5: DS2100 FUNCTIONAL OVERVIEW 
PAGE 5-6    C27750-001 
5.3  Power Interface Section 
5.3.1  High Power Section Description 
The high power supply section has the following features: 
 Three Phase a.c Operation 
 Direct Off-Line 230 V r.m.s to 460V r.m.s. +10% Operation 
 Soft Start (a.c. Inrush Current Limiting) 
 Input MOV Transient Protection 
 Internal Regeneration capability (μA units only) 
 Drive Ready Relay 
 Provision for External Regeneration Resistor 
 Integral Heat Sink and Cooling Fans 
 24V Logic Backup (mandatory on μA size units) 
These features are described in the next sections. 
The high power supply section may be divided into functional blocks: 
•  High voltage rectification and filtering 
•  Soft-start of a.c. mains power-on 
•  Low voltage control power supply 
•  Regeneration circuit 
•  Monitoring and fault logic circuits 
WARNING - The high power section contains large capacitors that maintain high 
voltage on the DC+ to DC- terminals for several minutes after input power is 
removed, if the regeneration circuit is not operating normally. Wait at least 5 
minutes for the μA sizes (6 minutes for the A-D sizes) after power shutdown for 
capacitors to discharge. Then use a voltmeter to check for safe voltage from the 
DC+ terminal to the DC- terminal before contacting terminals or commencing any 
service or maintenance activities to ensure no lethal voltages are present. Failure to 
follow this procedure may result in serious personal injury or death. 