APPENDIX C – RESTART INTERLOCK CIRCUITS  C-14 
CDS7324 (FORMERLY LSF-0819)   
Rev. A  INSTALLATION & USER’S MANUAL 
C.9   EXTERNAL CONSISTENCY CHECKS 
The following consistency checks must be made outside of the drive (e.g. by a PLC). 
•  “Channel 1 verification” 
 The external system must monitor this output signal for consistency with its input signal 
 Channel 1 (C.4.1.1). 
•  “Channel 2 verification” (if used) 
 The external system must monitor this output signal for consistency with its input signal 
 Channel 2 (C.4.1.2). 
•  Monitoring by a standard Programmable Electronic System 
•  Minimum functional requirements 
 The automatic monitoring shall, on discovering a fault, disconnect the line contactor and 
 prevent a new start until the fault has been removed 
 The transition of the monitoring signal shall be checked automatically: 
 - At start up and 
 - During each stopping and starting sequence. 
•  Wiring requirements to avoid common mode failures 
The external cable to RESTART INTERLOCK connector must be protected against 
mechanical damage according to the safety requirements of EN ISO 13849-2:2003, 
 tab. D.4 (prEN 954-2) in order to prevent short circuits. 
•  Software verification 
Following safety related principles; it is necessary to verify the software and give 
 instructions on following revisions. 
•  Modification of software 
The manufacturer shall write a warning in the software close to the part of program 
 concerning the safety function that this part must not be deactivated or modified for 
 safety reasons (see also clause 3.7.7 of EN 292-2) 
•  Other requirements 
 The output of the PLC to the line contactor shall be periodically tested by monitoring the 
 consistency of the NC contact of the line contactor. 
•  Protection of program 
 The program shall be monitored by e.g. a watchdog 
 The program shall be, in permanent memory, protected against electrical interference and 
 shall be equipped with a start-up test procedure. 