User`s manual
APPENDIX F – DEVICENET
TM
 MEZZANINE CARD  F-2 
CDS7324 (FORMERLY LSF-0819)   
Rev. A     INSTALLATION & USER’S MANUAL 
F.4  MacID & Baud rate 
MacID and Baud rate are software settable through the standard DeviceNet object. 
Default MacID is 63. Supported MacID’s are 0-63. 
Default Baud rate is 125. Supported Baud rates are 125, 250 and 500. 
F.5  Initial Motion Setup 
For the motion to be controlled over the fieldbus the following setup must be done: 
  On the ‘System Setup’ page, DeviceNet must be selected in the Fieldbus window, or the 
parameter FIELDBUS_INTERFACE must be set to 1. 
  The Fieldbus Scaling Factors (see below) only influence Move 1, so Move 1 must be selected 
either through the digital inputs or by setting the parameter GUI_PROFILE_SELECT to 1 or by setting 
the bit 0 in the CMND_WORD. 
  To start the motion, a start signal must be given either through the digital inputs, or by setting 
the parameter GUI_START_CMND to 1 or by setting bit 7 in the CMND_WORD . 
Note that if the drive is power-cycled, GUI_PROFILE_SELECT, GUI_START_CMND and 
CMND_WORD will revert back to 0, so these parameters must be set on every power-up. 
Note that CMND_WORD and STATUS_WORD are available on the implicit I/O to ease PLC integration 
and minimize service channel (explicit messaging) traffic. 
F.6 Fieldbus Scaling Factors 
The 5 field bus scaling factors provides an easy, safe, way to command the drive over the fieldbus. 
The scaling factors work on the set points of Move 1 as simple gain factors from 0 to 1. 
Example: 
  Move 1 Target position has been set to 100mm. 
  By varying the FIELDBUS_POS_SCALE_FACTOR between 0 and 1, the drive will position the 
actuator to any position between 0 and 100mm. 
  Note that a set point change only takes place if the START command is 1. Leaving the START 
command at 1 turns the drive in to a command follower. The START command can also be controlled 
over the fieldbus by writing to the GUI_START_CMND parameter. 