User manual
Fire Supervisory/Trouble (Resetting Smoke Detectors) 
Many smoke detectors "latch on" and illuminate a built-in indicator when trig-
gered. This feature allows you to determine which detector caused the alarm. If a 
smoke detector remains latched after resetting a fire alarm activation, the yellow 
TROUBLE indicator will be lit. 
1.  Check all smoke detectors for the presence of a latched condition to 
determine which detector triggered the alarm. If all detectors appear 
normal, a wire may be broken or shorted. Call for service. 
2.  Press Key 7 and hold for three seconds. The system will attempt to reset 
the smoke detectors. If the smoke detector(s) did not reset, the keypad will 
continue to indicate the TROUBLE condition. Call your security company 
representative for service. 
NOTE 
If a fire alarm is active, smoke detectors cannot be manually reset until the 
fire alarm is reset. 
Testing The Fire System 
All devices in a Fire Alarm system should be tested monthly except as described 
in NFPA 72 chapter 7-3-2. If the Bell Test on page 1-13 does not test the fire 
alarm bell, then follow these steps: 
1.  Notify the Central Station or the appropriate authorities that you are about to 
perform a fire system test. 
2.  Press and hold for three seconds the Keypad Panic Key 
(see FIGURE 1-1) that is designated as the Fire Panic Key. The Fire 
Alarm should go off. 
3.  Enter your passcode and press Reset (*) to silence the alarm. 










