5.7 DETERMINING THE FLUE LENGTH
IMPORTANT. The boiler must be installed in a vertical position in accordance to the installation instructions.
STANDARD FLUE KITS
Horizontal Flue Terminal RSF303 (600mm long) -contains:Flueturret,nontelescopicsinglepieceueincorporatingaterminal
and inner rubber wall seal.
Extension Kit RSF341 -contains:1metrelengthofuepipe(Functionallength950mm),1supportbracket.
When extension kits are used the ue duct must incline 1.5 degrees away from the appliance, to allow the condensate to drain back to
the boiler and out of the condensate drain. It is recommended that a support bracket is tted on every 1 metre of pipe work used and the
bracket is located as close to the collar as possible. The bracketing must ensure a 1.5 degree fall back to the appliance.
Only use water as a lubricant during assembly.
Thehorizontaluekitterminalisclassedaspartofthemaximumuelength.
Once the ue is installed it is IMPORTANT that the white air duct protrudes from the aluminum spinning by at least 17mm.
The gap between the spinning and the white air duct MUST be sealed with sealant to create an adequate seal.
ItisIMPORTANTthatallattachmentsarettedinaccordancewiththeinstallationinstructionsprovidedinthismanual.
TheTURRETsuppliedintheHorizontalFlueKits(RSF303&RSF305)hasanuppercombustionsamplepointwithascrewcap
sealandalowerairsamplepointwithanairstopperseal.Ensureallcaps&sealsareinplace.
Additional Termination KitsavailableforusewiththeseHorizontalFlueKits(RSF303&RSF305)
FlueDeectorKit(RSF300) Theresistanceistheequivalentof1metreofuepipeandthereforemustbedeductedfrom
anymaximumuelength
Total Maximum Permissible Horizontal Concentric Flue Length combining both Horizontal Flue Kits and Extension Kits
(Measuredfromcentrelineoftheturrettotheoutsidefaceofthealuminiumuecollar(RSF060))
24 kW appliances TotalMaximum:8metres-minusanyuekitoptions
30 kW Appliances TotalMaximum:7metres-minusanyuekitoptions
Total Maximum Permissible Vertical Flue Length
24&30kWAppliances Total Maximum: 7.5 Metres - minus any 90º bends
Minimum Horizontal Flue Lengths (Centrelineofturrettooutsidefaceofthealuminiumuecollar(RSF060))
Rear Flue - 191mm
Side Flue - 236mm (with minimum 2.5mm clearance)