Operation Manual

17
section 5 - installation instructions
5.8
DETERMINING THE FLUE LENGTH
5.9 CUTTING HORIZONTAL FLUE TERMINAL RSF303 (600MM LONG)
10mm
Mark cut length =
A or B + 47mm from terminal lip
1. Measurefromtheouterterminalliptoendofouterue.Markthe
required cut length (A or B + 47mm) around the circumference of the
outerueandcutfollowingthemarktoensureitscutsquare.
2. Dress the cut end to make sure all burr’s are removed and the cut
edge is in its original shape.
3. Mark the inner tube 10mm longer than the outer tube around its
circumference and cut following the mark to ensure its cut square.
4. Remove all burrs and place a light chamfer on the outer edge to aid
assembly.
Centre of turret to edge of turret = 100mm
Turret has a ue insertion of 30mm
The white outer ue tube must protrude the wall by 17mm.
From centreline of turret to wall. Rear mount 155mm, side (including clearance) 200mm
NOTES
REAR
Fit
to wall
A
Flue length measured from outer terminal lip
to end of outer ue
A or B + 47mm
SIDE
Fit
to wall
B
Minimum clearance 2.5mm
WALL
WALL
FIGURE 1
REAR FLUE
Cutuelength=distancefromedgeofturrettooutsideof
wall dimension A + 47mm.
Note. Minimum dimension A which can be accommodated is
91mm.
SIDE FLUE
Cutuelength=distancefromedgeofturrettooutsideof
wall dimension B + 47mm.
Note. Minimum dimension B which can be accommodated is
136mm (with minimum clearance of 2.5mm).