section 5 - installation instructions
5.10 INSTALLING THE FLUE
FITTING FLUE THROUGH THE WALL
1. Ensure the seam and the outlet terminal are
atthetopandttedasshown.
2. OncetheueisinstalleditisIMPORTANT
that the white air duct protrudes from the
aluminium spinning at least 17mm.
Note. If less than 50% of the length of the ue is
internal the ue should be tted from outside.
3. Fittheinternalsealingubbertotheue
(leave loose) and check protrusion externally
of the white air duct is 17mm.
4. Fit the turret as below
FITTING THE TURRET
1. Ensuretherubbersealisttedcorrectlyontheappliancemanifoldandthatalluesealsareundamaged.
2. Holdtheuermlyandpushtheturretonuntilithastravelled30mmontotheuepipeandisfullyengaged.Makesurethe
uehasnotrotatedormovedforwardduringttingandtheueseamisuppermost.
3. Pushtheturretintothemanifoldensuringtheupperplasticlipisushwiththetopofthemanifold.
4. Fullyengagetheclamplocationsectionintothemanifoldlocationholes.Rotatedownontoturretange.
5. Secure clamp to appliance using securing screw.
6. Ensureallsamplepointsareaccessibleandallsampleplugsandcapsaretted.
7. Fullyengagetheueintotheturretandslideinternalubbertowall.
8. The gap between the spinning and the white air duct MUST be sealed with sealant to create a seal.
Flue Outlet
C
A
A - Duct Assembly
B - Flue Turret
C - Turret Clamp
D - Seal
Flue Outlet
D
B
Retaining
screw
Clamp Lugs
Sample points
WALL
Spinning
Fill with
sealant
17mm min
Internal Sealing
Flubber
Fill with
sealant
5” hole