Document No. 996-140-000-9 Issue 9 FIRE 6.
MORLEY-IAS FIRE 6.21 User Manual Table of Contents 1 INTRODUCTION ......................................................................................................................... 4 1.1 Notice ...................................................................................................................................... 4 1.2 Warnings and Cautions......................................................................................................... 4 1.3 National Approvals ........
FIRE 6.21 User Manual 4.7.4 MORLEY-IAS Editing a Pattern ..............................................................................................................32 4.8 Event Logic ...........................................................................................................................33 4.8.1 The Event Logic Sequence .............................................................................................33 4.8.2 The Event Logic Editor .........................................
MORLEY-IAS FIRE 6.21 User Manual 1 Introduction 1.1 Notice The material and instructions covered in this manual have been carefully checked for accuracy and are presumed to be correct. However, the manufacturer assumes no responsibility for inaccuracies and reserves the right to modify and revise this document without notice. These instructions cover the use and operation of the ZX Windows Configuration Tool.
FIRE 6.21 User Manual 2 Description 2.1 Product Features MORLEY-IAS The following features are provided by the PC Programming Tool: 1. Programming the ZX range of fire panels (ZX1e/ZX1Se, ZX2e/ZX2Se, ZX5e/ZX5Se) 2. Report Printout of Configuration Settings 3. File Storage of Configuration settings for use by other applications software 4. Report Printout of the panel Event Log 5. Loop and Battery Calculation 6. Diagnostics. NOTE: FIRE 6.
MORLEY-IAS FIRE 6.21 User Manual 3 Installation 3.1 How to Install the Application The application is installed as a Windows program. On the CD there is a folder called ‘SW993-738 ZX Config Tool’, which contains a single executable file. Run this file (by double-clicking or else by starting it in the Start menu’s ‘Run…’ option) and follow all the prompts that appear. This will install FIRE 6.nn in the Start menu.
FIRE 6.21 User Manual MORLEY-IAS 4 Operation 4.1 Starting the Program The program can be started from the shortcut icon displayed on the desktop. When the program is first started a splash screen displaying the company logo will be shown. The following window will appear which prompts either to start a new project or to access an existing project by opening a configuration file. Fire 6.
MORLEY-IAS 4.2 FIRE 6.21 User Manual Opening a File / Creating a New File 4.2.1 New File Selecting ‘New’ from the toolbar or ‘File’ menu creates a new blank project. At this point, no devices are configured on any loops, there are no text descriptions for addresses or zones, and there are no configured event logic sequences. A number of defaulted onboard outputs are created, according to the capability of the panel, and each such output is allocated a unique ringing pattern number.
FIRE 6.21 User Manual 4.3 MORLEY-IAS Main Screen Features 4.3.1 Menu Bar and Speed Buttons Once the above choices have been made, the main screen appears.
MORLEY-IAS 4.3.1.1 File Handling Menu (FILE) The top left-hand corner of the main form holds the menus and the file handling speed buttons: 2 1 4.3.1.2 FIRE 6.21 User Manual 3 4 5 6 7 8 These buttons are: No.
FIRE 6.21 User Manual 4.3.1.3 4.3.1.4 Utilities Menu (TOOLS) The following utilities are provided in the tools menu: a) Contact Management b) Loop & Battery Calculator c) Options 1 Panel Communication Menu (COMMUNICATIONS) Panel Communications area of the toolbar.
MORLEY-IAS FIRE 6.21 User Manual 4.3.2 Main Screen Views 4.3.2.1 General Options This is shown below. This is the default screen, which appears whenever a new project is created or a configuration file is opened. It also appears when the General Options menu item is selected.
FIRE 6.21 User Manual 4.3.2.2 MORLEY-IAS Device Loop Editor This is shown below. The device loop editor displays details for one loop (which may be one of the main loops or the Peripheral Loop), and is selected from the appropriate speed button, or by selecting Edit in the menu bar, then Loops, then the appropriate loop.
MORLEY-IAS 4.3.2.3 FIRE 6.21 User Manual Zone Text Editor This is shown below. The zone text editor displays textual descriptions for all zones and is selected from the ‘Zone Text’ speed button, or by selecting Edit in the menu bar, then Zone Text.
FIRE 6.21 User Manual 4.3.2.4 MORLEY-IAS Outputs Editor A 5-loop panel has 6 onboard outputs, and all other panels have 4. If the panel does not have 6 onboard outputs then there will be 2 outputs marked as reserved in the editor. The settings for these should not be changed. The outputs editor displays details of all outputs (both onboard the panel and associated with loops) and is selected from the Outputs speed button, or by selecting Edit in the menu bar, then Outputs.
MORLEY-IAS 4.3.2.5 FIRE 6.21 User Manual Ringing Patterns Editor This is shown below. The ringing patterns editor displays the complete list of ringing patterns and the full zonal settings for one highlighted pattern and is selected from the Patterns speed button (F9), or by selecting Edit in the menu bar, then Ringing Patterns.
FIRE 6.21 User Manual 4.3.2.6 MORLEY-IAS Event Logic Editor This is shown below. The event logic editor displays all settings for 60 event logic sequences, and is selected from the Event Logic speed button (F10), or by selecting Edit in the menu bar, Event Logic.
MORLEY-IAS 4.4 FIRE 6.21 User Manual Loop Configuration 4.4.1 A Quick Tour of the Loop Editor The Loop editor is shown below, and contains the following features: Device selector Loop configuration grid Loop identifier Insert/ remove mode selector buttons - Loop identifier: Displays the loop number (or ‘Peripherals’) - Mode selector buttons: Toggle these to select device insertion or removal mode. The appropriate button being highlighted indicates the mode.
FIRE 6.21 User Manual MORLEY-IAS The Loop Configuration Grid contains the following columns: Name Description Address The number of the address, sequentially increasing from 1 to the maximum number of devices for a loop (which depends upon the device manufacturer). This column cannot be changed. Description Up to 20 characters of device location text can be entered here. Device Type Information about the specific device inserted at the address. Defaults to ‘’ if no device is inserted.
MORLEY-IAS FIRE 6.21 User Manual 4.4.3 Inserting a Device This is done by following these steps: 1. Ensure the editor is in insertion mode by clicking the ‘Insert’ button. 2. Drop down the device list and select the required device. 3. If applicable, specify whether the device has a base sounder fitted. 4. To insert the device, double click on the address number required or alternatively highlight the required address and then press the INSERT key.
FIRE 6.21 User Manual MORLEY-IAS 4.4.5 Inserting Multi-Input Devices When a multi-input device is inserted, and sufficient addresses are left on the loop, an option is given to insert the device in expanded mode. In expanded mode, each input point of the device is assigned to a separate loop address, starting with the address originally selected for the first input and increasing sequentially for each additional input.
MORLEY-IAS FIRE 6.21 User Manual 4.4.7 Changing Device Settings 4.4.7.1 In general, settings can only be modified if they are applicable to the inserted device. The following device settings may be changed in the Loop Editor where appropriate: Input Actions Switching devices such as MCP have a default input setting of ‘Confirmed Fire’.
FIRE 6.21 User Manual 4.4.7.2 MORLEY-IAS Input Actions for Unexpanded Multi-Input Devices Where more than one input shares the same address, the grid displays the input action only for the first input. Selecting this cell brings up a mini-editor box listing all the inputs on the device, and allowing each one to be set independently: 4.4.7.
MORLEY-IAS 4.4.7.5.2 FIRE 6.21 User Manual Laser Smoke Detector This device has 9 detection levels numbered 1 to 9, which can be used to adjust the detection sensitivity. (for more information, see device data sheets). 4.4.7.6 Hochiki Multi-Sensors The Hochiki Multi-Sensor is supported as detailed below from panel software version 824 onwards.
FIRE 6.21 User Manual 4.5 MORLEY-IAS Editing Zone Text The Zone Text Editor is shown below: To make best use of the screen, the range of zones is divided into an upper and lower sub-range. Using the vertical scrollbar, the TAB, ARROW and PAGE UP/PAGE DOWN keys and/or the mouse, a cell may be selected, into which up to 20 characters of text may be entered to describe a zone.
MORLEY-IAS 4.6 FIRE 6.21 User Manual Outputs 4.6.1 A Note about Outputs There are two types of output: relays and sounders. These outputs can be classed as being either onboard, loop or peripheral. All of the outputs associated with a multi-output device are grouped at a single loop address; each output is then allocated a sub-address. Single-output devices have their outputs on sub-address 1. Each type of panel has its own configuration of Onboard Outputs; e.g.
FIRE 6.21 User Manual MORLEY-IAS 4.6.2 The Outputs Editor A screenshot of the outputs editor is shown below: These columns are only visible when using Hochiki devices These columns are provided for information purposes only and cannot be changed These columns are only visible when using Apollo devices Onboard: Address 0: 2 relays, 2 sounders Hochiki Loop: Address 4: Address 5: Sensor with base sounder. CHQ-AB beacon with base sounder. Peripheral: Address 1: 4-way sounder card.
MORLEY-IAS FIRE 6.21 User Manual 4.6.3 Configuring Output Settings Where an output setting may be modified, as indicated in the above table, this is done simply by accessing the appropriate data cell on the grid and entering the desired setting. Note that an output may be assigned to any pattern number or event number within the limits of the panel. 4.6.4 Hochiki Sounders A Hochiki sounder can have settings for volume and frequency.
FIRE 6.21 User Manual MORLEY-IAS 4.6.5 Apollo Discovery Sounder Beacons The Discovery Sounder Beacons (types 58000-005, 58000-007) and Sounder Beacon Base (type 45681-393) have settings for Level (volume) and Mode (tone pair). The volume can be set to a numeric value between 1 and 7 (default is 3) and sounder mode between a numeric value of 1 and 15 (default is 14).
MORLEY-IAS 4.7 FIRE 6.21 User Manual Ringing Patterns 4.7.1 Adding a New Ringing Pattern Each output may optionally be assigned to a ringing pattern. This can be used to describe the way each zone triggers the ringing pattern. The ringing pattern can then be assigned to an output in the Outputs Editor using the ringing pattern column. The way in which the ringing pattern will operate can then be set up in the Ringing Patterns Editor.
FIRE 6.21 User Manual MORLEY-IAS 4.7.2 The Ringing Patterns Editor This editor allows the configuration of zonal range settings for existing ringing patterns. Note that new ringing patterns are added by assigning an unused ringing pattern number to an output in the Outputs Editor. The Ringing Patterns Editor is shown below: The ringing pattern being edited Contains the zonal settings for the chosen ringing pattern Ensures that a zonal range is added to the ringing pattern.
MORLEY-IAS FIRE 6.21 User Manual Entering values into the cells of the grid alters the settings.
FIRE 6.21 User Manual 4.7.4.3 MORLEY-IAS Deleting A Zonal Setting In previous versions of the configuration tool a facility was provided to delete a zonal setting. This has now been removed as the same effect can be achieved by editing the zonal range (see above) and setting it to the OFF mode. The advantage of this method over the old method is that the deleted zonal range rather than implicitly set to OFF is now explicitly set to OFF and remains in the grid.
MORLEY-IAS FIRE 6.21 User Manual 4.8.2 The Event Logic Editor This is shown below: It consists of: - A grid where data is entered, with the following columns: Name Seq Logic E1 E2 Description The sequence number (cannot be changed). The logic to use. There is a choice of: AND = if all of the causal events entered occur OR = if any of the causal events entered occur NONE = ignore this sequence The causal event numbers. This defaults to 0, which means don’t include in the logic. (i.e.
FIRE 6.21 User Manual MORLEY-IAS 4.8.3 Testing Events It is possible to enter contradictory data into the event logic editor, which would create invalid sequences. There are several ways in which bad data may be entered; perhaps one of the most common is for the effect event in sequence to have the same number as one or more of its cause events. The ‘Test Logic’ button can be used to scan through all 60 sequences searching for this phenomenon.
MORLEY-IAS FIRE 6.21 User Manual Any text entered will be saved to the configuration file, however it is only possible for the ‘customer name’ and ‘Service Contact Number’ to be transferred to the panel (if the panel software version is 818, or later). There is no specific format for entering data for any of these. 4.9.3 Panel Details 4.9.3.1 Panel Software ID This cannot be manually changed and is automatically updated whenever a panel connection is made.
FIRE 6.21 User Manual MORLEY-IAS 4.12 Panel Communications 4.12.1 Comms Setup 4.12.1.1 Communications Port The communications port applies both to direct and remote connections. It defines the serial port through which the communication is achieved. Internal Modems: Internal modems require a driver to be installed. The driver is essential as it defines the interface necessary for programs to communicate with the modem. It will provide a ‘virtual’ serial port, which must then be chosen.
MORLEY-IAS FIRE 6.21 User Manual 4.12.1.4 Allow Remote Evacuation This setting is only relevant to the hardware key protected ‘dial-up’ facility. Remote evacuation can only be performed if this option is checked. This is a safety feature, which prevents accidental evacuation of a remote fire system. This setting applies to the ‘Interactive Panel Display’. 4.12.2 Linking To a Panel A physical connection should exist between the panel and computer before an attempt is made to communicate.
FIRE 6.21 User Manual MORLEY-IAS 4.12.4 Configuring the PC from a Panel To retrieve the configuration of the panel, follow these simple steps: 1. 2. 3. Ensure there is a physical communications path between the panel and the computer. Save the existing configuration file if the settings it contains will be required later. Placing the panel in ‘Commission/PC/Configure’ mode can reduce communication transfer time.
MORLEY-IAS FIRE 6.21 User Manual 4.12.5.1 General Panel Information The system provides information regarding the following: a. b. c. d. e. f. Panel Name (Only supported from panel software version 814) Service No (Only supported from panel software version 814) Panel software version The manufacturer of loop devices The number of loop drivers fitted The number of zones supported by the panel 4.12.5.
FIRE 6.21 User Manual MORLEY-IAS 4.12.5.3 Interactive Panel Fascia This provides a graphical layout of the panel front including the LCD display, control keys, normal keys and status LEDs. The fascia will automatically change to resemble the installed system. It is possible to interact with the installed system by using either the mouse (by clicking on the fascia buttons) or by using the keyboard. Keyboard controls: PC Key Panel key 0..9 A..Z 0..9 A..
MORLEY-IAS FIRE 6.21 User Manual 4.12.5.4 Panel Device Tree The panel device tree shows the state of every addressable device learnt. There are four different icons that are used to represent the state of a device and these are: The icon indicates the status of the device as recognised by the fire panel. Notes: a. The panel tree will only show the status of devices already learnt and at the time when the interactive display was first shown. b.
FIRE 6.21 User Manual 4.12.5.5 MORLEY-IAS Inspecting a Device The interactive panel display provides the facility to perform a detailed device inspection. This is done by first selecting a device in the panel tree and then choosing ‘Inspect Device’. The detailed device inspection is separated over two areas.
MORLEY-IAS FIRE 6.21 User Manual 4.12.5.6 Enabling/Disabling Devices Using the device tree, the panel can be instructed to enable/disable the monitoring of the return signal from a device. This is achieved by selected a device, bringing up the popup menu and selecting either enable/disable, e.g. 4.12.6 Panel Event Log A facility is provided to retrieve the panel history log. The log entries are displayed as they are received and the display can be filtered by fire/fault events. 4.12.6.
FIRE 6.21 User Manual MORLEY-IAS 4.12.6.2 Print Log The ‘Print Log’ option provides a printer dialog, through which it is possible to make a hard copy of the log retrieved. NOTE: The operating system must have the appropriate printer driver installed to allow printing from the application. 4.12.6.3 Stop/Continue The ‘Stop/Continue’ option allows the retrieval of the history log to be suspended. This is useful if not the entire history log is required. 4.12.6.
MORLEY-IAS FIRE 6.21 User Manual 4.13 Contact Management A facility is provided to store the details that relate to each project. This can be used to contain things such as: - The person responsible for the site The site location The details for connecting remotely to the panels of a site (if applicable) The passwords required for panel access. This information can be accessed at any time, regardless of which project is currently open and is maintained by the application.
FIRE 6.21 User Manual MORLEY-IAS 4.13.2 Editing Contacts The Contacts form, which opens when the Contact Details menu item is selected, is shown below. It contains a list box on the left-hand side, which lists all the records in the database, and a main panel in which all fields for the selected record can be viewed and edited. A Contact record contains the following compulsory fields, which must be filled in, or FIRE 6.
MORLEY-IAS FIRE 6.21 User Manual 4.13.3 Inserting New Entries To insert a new entry, click on the ‘Insert’ button. A dialog box will appear, into which the title of the new entry must be inserted: When ‘OK’ is clicked the main Contacts form will display the new title and the other fields may be filled in. NOTE: FIRE 6.16, or later, will not allow insertion of a new entry unless all the compulsory fields are filled in for the existing entry in view. 4.13.
FIRE 6.21 User Manual MORLEY-IAS 4.14 Printing and Previewing Reports 4.14.1 Methodology A print preview and print facility is provided for each of the editors, namely: All main device loops (including Peripheral loop), each loop being printed as a separate section Zone text Sounder and other output settings Ringing patterns Event Logic General panel details Unlike FIRE 6.0, which used Windows Notepad and required this to be configured for font size, orientation, etc.
MORLEY-IAS FIRE 6.21 User Manual 4.14.3 Previewing a Report Selecting ‘Preview Report’ displays a window in which any one section of the project data may be previewed (when the window is opened, the ‘General Options’ section is displayed by default). A column is included at the left-hand side containing miniature images of all the other data sections, which can be selected to view different sections of the data.
FIRE 6.21 User Manual MORLEY-IAS 5 Upgrading Existing Panels 5.1 Introduction 5.2 From Fire 6.11, a facility is provided for recovering the zone text and device text from panels containing software dating back to version 400. How to Perform the Upgrade This procedure will guide you through the process of upgrading your panel: 1. Start a new configuration, ensuring that the number of loops and device manufacturer will be correct for the panel after it has been upgraded. 2.