Installation Manual

11
Sealed / Flooded Select
Flooded batteries require more vigorous charging to avoid strati-
fication, and sealed batteries require precise control to avoid out-
gassing. The SunLight constant voltage setpoints are 14.4 volts
for flooded batteries, and 14.1 volts for 12 volt sealed batteries.
See Section 6.4-7 for more information.
LED Indicators
See Section 5.0
Low Voltage Disconnect (LVD)
If the battery falls below 11.7 (or 23.4) volts, the load is discon-
nected from the battery to protect against harmful deep dis-
charges. A one minute delay prevents load disconnects from
transients. The load is automatically reconnected when the bat-
tery voltage recovers to 12.8 (or 25.6) volts.
Battery Disconnect
If the battery is disconnected during the daytime, the PV array
will continue to provide power to the controller. The SunLight will
immediately go into PWM and provide power at a constant volt-
age to the load. This will continue as long as sufficient power is
available from the PV array.
Parallel Controllers
Morningstar controllers work very well in parallel configurations.
No blocking diodes are required. The only constraint is that each
controller must have an independent and separate PV subarray
and load. Make sure that each controller’s rating for PV and load
current is not exceeded.
Auxiliary Generators
Engine generators and other sources of power may be connect-
ed directly to the battery for charging. It is not necessary to dis-
connect the SunLight from the battery. However, do not use the
SunLight to regulate these other generators.
Reverse Current
The SunLight prevents the battery from discharging through the
PV array at night. There is no need to install a blocking diode for
this purpose.