ProStar Testing Instructions

SunLight Testing Instructions Page 1 of 3 Revision 1.0
Morningstar Corporation 3 September 1999
Testing Morningstar SunLight Controllers
Notes:
- Due to the nature of the SunLight controllers, it is possible only to determine whether the
unit is functioning properly. It is not always apparent what component has failed or the
cause for the failure. It is left up to the technician to determine the cause for the controllers
failure based on evidence present at the site (i.e. burned leads, excessive loads, evidence of
short circuits on load leads, more PV current than the controller is rated for etc.)
- It is difficult to completely verify the operation of the SunLight controller in less than 2 full
days due to the nature of the controller. However the operation of the controller can be
verified to a 95% confidence level with the test procedures outlined below.
- The procedures outlined below assume a basic knowledge of electric circuits and the
necessary safety precautions to be used when working with live circuits present in solar
energy systems.
- All voltages will be given for a 12V nominal system. For a 24V nominal system, all voltages
should be double.
Recommended Tools:
- Digital Multi Meter (frequency and duty cycle measurements are helpful)
- Flat Bladed Screwdriver
- A lighting load (a type 1156 automotive brake lamp works well for 12V systems)
- A battery bank (of appropriate voltage for the controller)
- A solar array in full sun and/or a Power Supply (of appropriate voltage for the controller)
- Wire for connections to the SunLight.
Test Procedure:
1) Connect the battery and a load to the SunLight.
2) Set the load switch to any setting desired.
3) Verify the load works by pressing the test button.
4) Wait 5 minutes for the load to go off
5) Connect a power supply (set to 15V) or a PV panel placed in full sun to the Solar Input
Terminals (Terminals #4 and #3). Be sure to observe correct polarity.

Summary of content (3 pages)