Product Manual

Mechanical
Powerterminalswiresize(max.)
 Solid #10AWG/5mm2
 Multistrand #10AWG/5mm2
 Finestrand #10AWG/5mm2
 TerminalDiameter 0.210in/5.4mm
Powerterminalstorque(max.) 10.6in-lb/1.2Nm
Dimensions seeinsidefrontcover
Weight(unpacked) 8oz/0.23kg
Certications
ISA12.12.01NonincendiveElectricalEquipmentforUsein
ClassI,Division2Hazardous(Classied)Locations,Groups
A,B,C,D.2007/04/12.
CSAC22.2#213Non-IncendiveElectricalEquipmentforUse
inClassI,Division2HazardousLocations.1987/01/03.
EMCDirectives
Immunity:EN61000-6-2:1999
Emissions:EN55022:1994withA1andA3ClassB1
Safety:EN60335-1andEN60335-2-29(batterychargers)
Charts
Fuse Chart
Wire Gauge (AWG) Max. Fuse Size*
14 15Amps
12 20Amps
10 30Amps
*per2011NECNFPA70,Article240.Forcopperwireonly.
Refertothewirechartsonpage41forappropriate wiresize.
UL1741 INVERTERS, CONVERTERS, AND
CONTROLLERS AND INTERCONNECTION SYSTEM
EQUIPMENT FOR USE WITH DISTRIBUTED ENERGY
SOURCES, FIRST EDITION, REVISION THROUGH AND
INCLUDING NOV 7, 2005
CSA C22.2 No. 107.1-01
3094762
RoHS
Compliant
2002/95/EC
7.0TECHNICALSPECIFICATIONS
MORNINGSTARCORPORATION 43
12 Volt Nominal Wire Chart
amps
One-way Wire Distance (feet)
Wire Gauge (AWG)
One-way Wire Distance (meters)
Wire Gauge (mm
2
)
14 12 10 8 6 2.0 3.0 5.0 8.0 13.0
2
70 112 180 287 456 21 32 53 85 139
4
35 56 90 143 228 10 16 26 42 69
6
24 38 60 96 152 7 10 17 28 46
8
18 28 45 72 114 5 8 13 21 34
10
14 23 36 57 91 4 6 10 17 27
12
12 19 30 48 76 3 5 8 14 23
14
10 16 26 41 65 3 4 7 12 19
16
9 14 23 36 57 3 4 7 10 17
18
8 13 20 32 51 2 3 6 9 15
20
7 11 18 29 46 2 3 5 8 13
3%Voltagedrop,Annealedcopperwireat20°C
24 Volt Nominal Wire Chart
amps
One-way Wire Distance (feet)
Wire Gauge (AWG)
One-way Wire Distance (meters)
Wire Gauge (mm
2
)
14 12 10 8 6 2.0 3.0 5.0 8.0 13.0
2
140 224 360 574 912 42 64 107 171 278
4
70 112 180 286 456 21 32 53 85 139
6
48 76 120 191 304 14 21 35 57 92
8
36 56 90 144 228 10 16 26 42 69
10
29 45 72 115 182 8 12 21 34 55
12
24 38 60 96 152 7 10 17 28 46
14
20 32 51 82 130 6 9 15 24 39
16
18 28 45 72 114 5 8 13 21 34
18
16 25 40 64 101 4 7 11 19 30
20
14 23 36 57 91 4 6 10 17 27
3%Voltagedrop,Annealedcopperwireat20°C