TriStar Manual

20
Installation
In both settings (auto and manual), the push-button can be used to start and stop battery equal-
ization. If the selected battery charging setting does not have an equalization stage an equaliza-
tion will never occur, even if requested manually.
Equalize Switch 7
manual OFF
automatic ON
Switch 8: Ethernet Security
TheEthernetSecurityswitchenablesordisablescongurationoftheTriStarMPPT150Vsettings
through the Ethernet connection. When switch eight is set to disabled, write commands to the
TriStar MPPT 150V custom memory are not allowed. This a safety feature to prevent unintended
changes to custom settings, but it is not a replacement for proper network security.
Conguration via TCP/IP Switch 8
disabled OFF
enabled ON
NOTE:
Adjustment of network settings and custom set-points is always enabled via the RS-232 and EIA-
485 connections. The Ethernet Security switch only enables/disables remote conguration via
TCP/IP.
CAUTION: Risk of Tampering
The Ethernet Security settings switch does not block write commands to devices bridged via EIA-
485.
REMARQUE :
Le réglage des paramètres de réseau et des points de consignes personnalisés est toujours
activé par les connexions RS-232 et EIA-485. Le contacteur de sécurité Ethernet n’active/
désactive que la conguration à distance par TCP/IP.
PRUDENCE : Risque de tentative d’altération
Le contacteur des paramètres de sécurité Ethernet ne bloque pas les commandes d’écriture sur
les dispositifs reliés par EIA-485.