TriStar MPPT Installation and Operation Manual

27TriStar MPPT Operator’s Manual
Over-Current Protection and Disconnects
WARNING: Shock Hazard
Fuses, circuit breakers, and disconnect switches should never
open grounded system conductors. Only GFDI devices are
permitted to disconnect grounded conductors.
AVERTISSEMENT : Risque de décharge électrique
Les fusibles, coupe-circuits et interrupteurs ne doivent jamais
ouvrir les conducteurs du système mis à la terre. Seuls les
dispositifs GFDI sont autorisés à déconnecter les conducteurs
reliés mis à la terre.
Circuit breakers or fuses must be installed in both the battery and solar circuits. The protection
device ratings and installation methods must conform to NEC requirements.
The battery circuit fuse or circuit breaker must be rated to 125% of the maximum current or more.
The minimum fuse/breaker rating allowed for use with each TriStar MPPT model is listed in table
3-3.
Model Minimum battery circuit fuse/breaker rating
TS-MPPT-30 1.25 x 30 Amps = 37.5 amps
TS-MPPT-45 1.25 x 45 Amps = 56.3 amps
TS-MPPT-60 1.25 x 60 Amps = 75.0 amps
Table 3-3 Minimum battery circuit fuse/breaker ratings per NEC requirements
A disconnect is required for the battery and solar circuits to provide a means for removing power
from the TriStar MPPT. Double pole switches or breakers are convenient for disconnecting both
solar and battery conductors simultaneously.
Connect the Power Wires
WARNING: Shock Hazard
The solar PV array can produce open-circuit voltages in excess of 100 Vdc when
in sunlight. Verify that the solar input breaker or disconnect has been opened
(disconnected) before installing the system wires.
AVERTISSEMENT : Risque de décharge électrique
Le réseau PV solaire peut produire des tensions de circuit ouvert supérieures à 100 V cc
à la lumière du soleil. Vériez que le coupe-circuit ou l’interrupteur d’entrée solaire a été
ouvert (déconnexion) avant d’installer les câbles du système.