Fow Rates
The relationship between boiler ow rate
and temperature rise is according to the
formula:
Boiler output (Btu/h) = 500 x ow (USGPM)
x Rise (℉)
The following chart lists typical ow rates
for the Vitorond boiler:
Boiler Model MHB80 MHB160
20℉ USGM 17. 2 21.5
30℉ USGM 11. 5 14.3
General
The schematics on the following pages are to
be seen as guidelines only. They futher do not
display all system varieties, safety devices, or
concepts possible.
Clearances
A minimum of 2" circumferentail clearance from
non-insulated hot water pipes to combustible
construction must be maintained. In cases where
the pipes are insulated with pipe insulation
of appropriate and sufcient thickness and
insulation values, the above clearance may be
reducated to 0".
Waterside Flow