Honda 6.7 kVA Silenced Petrol Auto Sart Generator GE SX-7000 HBM

Table Of Contents
MADE IN ITALY
language
GENERATING SET
GE SX-7000 HBM
The images are for reference
Pag 1
04/2020
FEATURES
HONDA iGX engine with electronic speed governor
Electric and manual start
Automatic voltage regulation AVR
Engine shut down for low oil level (oil alert)
Automatic starter (auto-choke)
Circuit breaker
ELCB-GFI (Ground Fault Interruptor)
Supersilenced
Ready for connection to automatic transfer unit EAS
Meets EC directives for noise and safety
POWER RATINGS
*
Stand-By
single
-phase power
(LTP)
6.7 kVA (6 kW) /230V/ 29.1A
* PRP single-phase power 6 kVA (5.4 kW) /230V/26 A
Frequency 50 Hz
Cos j 0.9
* Powers declared according to ISO 8528
EnginE 3000 rPm
4 STROKE, OHV, NATURAL ASPIRATED
Model HONDA iGX 390
Stand-By net power 8.2 kWm (11.1 hp)
PRP net power 6.4 kWm (8.7 hp )
COP net power /
Cylinders / Displacement 1 / 389 cm³ (0.39 lt.)
Bore / Stroke 88 / 64 (mm)
Compression ratio 8.2 : 1
BMEP (Brake Mean Eective
Pressure : LTP - PRP)
/
Speed governor type Electronic
FUEL CONSUMPTION
110 % (Stand-by power) 3.5 lt./h
100 % to PRP 3.2 lt./h
75 % to PRP 2.4 lt./h
50 % to PRP 1.6 lt./h
COOLING SYSTEM
Total system cap. - only engine /
Fan air flow /
LUBRICATION SYSTEM
Total oil system capacity /
Oil capacity in sump 1.1 lt.
Oil consumption at full load /
EXHAUST SYSTEM
Maximum exhaust gas flow /
Max. exhaust gas temp. /
Maximum back pressure /
External diameter exhaust pipe /
ELECTRICAL SYSTEM 12 Vdc
Starter motor power /
Battery charging alternator cap. 1A
Cold start /
With cold start aid /
AIR FILTER Dry
Combustion air flow /
HEAT REJECTED AT FULL LOAD
To exhaust system /
To water and oil /
Radiated to room /
To charge cooler /
air cooled petrol single-phase electric start
DEFINITION
Valid declared powers up to the followings environmental conditions: temperature
25°C, altitude 100 meters above sea level)
LTP power: stand-by power: Maximum available power for use with variable loads for a
yearly number of hours limited at 500 h. No overload is admitted.
PRP power: continue power with variable loads. Maximum power for use with variable
loads for a yearly illimited nubers of hours.
COP power: continuous power with constant load. Maximum power for use with constant
loads for a yearly unlimited numbers of hours.
E
N
G
I
N
E
S
T
A
G
E
5