User Manual

Mosa reserves the right to change this specication without notice. For further information please contact the sales department.
© MOSA - Viale Europa, 59 - 20090 Cusago (Milano) - Italy -phone +39-0290352.1 - fax + 39-0290390466 E-mail: info@mosa.it Web site: www.mosa.it
GE12000KSX-GSAVRZGB 09/14
Standard
Equipment
Diesel
engine
Air cooling Electric
Starter
Battery
12V
Engine
protection
Low press.
shut down
Hight temp.
engine
shut down
Battery char-
ge indicator
Low fuel
indicator
Hours-meter Central
lifting eye
Synchronous
alternator
Automatic
voltage
regulator
Sockets ELCB-GFI Circuit
breaker
Thermal
shut off
Voltmeter/
frequenci-
meter
Predisposiz.
EAS/TCM
Local/Remote
Start selector
GENERATING SET
GE 12000 KSX/GS - AVR
QQ KOHLERQDieselQengineQ3000Qrpm
QQ EngineQprotectionQES
QQ Single-PhaseQsynchronousQalternator
QQ AutomaticQvoltageQregulatorQAVR
QQ Sockets:Q1x230VQ63AQ2P+TQCEEQ-Q1x230VQ32AQ2P+TQCEEQ
Q 1x230VQ16AQ2P+TQCEE
QQ ELCB-GFIQ(GroundQFaultQInterruptor)
QQ CircuitQbreaker
QQ SuperQSilenced
QQ ReadyQforQconnectionQtoQautomaticQtransferQunitQEAS
QQ MeetsQECQDirectivesQforQsafetyQandQnoiseQlevel
2000 / 14 / CE
TechnicalQdata GEQ12000QKSX/GSQ-QAVR
A.C.QGENERATIONQ-Q50QHzQQ-QQSingle-Phase synchronous alternator, self-excited, self-regulated
*Stand-byQsingle-phaseQpower
*PRPQsingle-phaseQpower
**Stand-byQsingle-phaseQpowerQ(optional)
**PRPQsingle-phaseQpowerQ(optional)
CosQj
InsulationQclass
13.5 kVA (12.1 kW) / 230 V / 58.7 A
12 kVA (10.8 kW) / 230 V / 52.5 A
13.5 kVA (12.1 kW) / 115 V / 117.4 A
12 kVA (10.8 kW) / 115 V / 104.4 A
0.9
H
* Output powers according to ISO 8528-1 ** NOT READY for connection to automatic transfer unit EAS / WITHOUT Automatic voltage regulator AVR
ENGINEQQ-QQ4-stroke diesel, direct injection, Air cooling
Model
*QStand-ByQnetQpower
*QPRPQnetQpower
Cylinders/QDisplacement
Speed
FuelQconsumptionQ(75%QofQPRP)
KOHLER KD 477-2
14.9 kW (20.3 HP)
13.5 kW (18.4 HP)
2 / 954 cm³
3000 rpm
2.8 l/h
* Potenze dichiarate in accordo con ISO 3046-1
GENERALQSPECIFICATIONS
TankQcapacity
RunningQtimeQ(75%QofQPRP)
IPQprotectionQdegree
*DimensionsQLxlxhQ(mm)
*DryQweight
**QMeasuredQacousticQpowerQLwAQ(pressureQLpA)Q
**QGuaranteedQacousticQpowerQLwAQ(pressureQLpA)
23 l
8.2 h
IP 23
1320x790x750 mm
297 kg
96 dB(A) (71 dB(A) @ 7m)
96 dB(A) (71 dB(A) @ 7m)
* Dimensions and weight without trolley/trailer / ** Acoustic power according to European Directive 2000/14/EC
Versions on
request
Q Version 230V/ 115V with:
- Sockets: 1x230V/ 32A 2P+T CEE - 1x230/ 16A 2P+T CEE - 2x110/ 32A 2P+T CEE - 2x110/ 16A 2P+T CEE
Options on
request
Q Earthing kit
Q Remote control TCM22
Q Automatic transfer unit (AMF) EAS 17-809
Q Tank locking cap
Q Trolley CTM300
Q Site tow CTL300
Q Road trolley CTV4
Factory
installation
options
Q Oil heater