26 3. Installation
3.8.3Grounding the SDIDU
TM
1. The SDIDU™ should be able to be connected to a system or building electrical ground
point (rack ground or power third-wire ground) with a cable of 36” or less.
2. Connect the grounding wire to either grounding point on the rear panel. Use
6-32x5/16 maximum length screws (not provided) to fasten the lug of the grounding
cable.
3. Connect the other end of the ground to the local source of ground in an appropriate
manner.
3.8.4Connecting the SDIDU
TM
to the PC and Power Source
1. Using the supplied power cable connector, pin 2 (labeled -V) should be connected to the
power supply terminal supplying -48 V dc, while pin 1 (labeled RET) should be connected to
the power supply return. Refer to Figure 3-17. Use of a power supply with an inappropriate
ground reference may cause damage to the SDIDU
TM
and/or the supply.
2
1
Figure 3-17. SDIDU DC Power Cable Connector
2. Connect the SDIDU
TM
power cable to the 48 V dc power supply, and place the
voltmeter probes on the unconnected SDIDU
TM
end of the power cable, with the
positive voltmeter probe on pin 2 (-V) of the cable connector and the negative probe
on pin 1(RET). The connector terminal screw heads may be used as convenient
monitor points. Refer to Figure 3-17.
3. Turn on the –48 V dc supply. Verify that the digital voltmeter reads between 44 V dc
and 52 V dc when monitoring the cable points specified above. Adjust the power
supply output voltage and/or change the connections at the power supply to achieve
this reading.
4. Turn the 48 V dc supply off.
5. Plug the SDIDU
TM
power cable into the SDIDU
TM
rear panel DC Power connector (DC
Input). Place the voltmeter probes on the cable connector terminal screw heads as