Datasheet

www.symcom.com • 800-843-8848 • fax: 605-348-5685
9
Available Models:
Auxiliary Products:
Com 4-20mA (for 4-20mA output)
RS485MS-2W (for limited Modbus
capabilities)
RM-1000/RM-2000 (remote displays)
Features:
Motor output power measurement
3 separate restart timers for rapid-cycle
protection, motor cool down and dry-well
recovery
Built-in 3-digit display for setup and
diagnostics
Last fault indication on display
Last 4 faults available on network or remote
displays
Optional remote displays (RM-1000 or
RM-2000) via Modbus communications
Limited Modbus capabilities
Adjustable underload trip delay
(network only)
Power factor measurement (network readable)
Run-hour meter (network readable)
4-20mA scalable output signal
A
pprovals:
777-AccuPower
The Model 777-AccuPower
is a fully-programmable 3-phase motor and pump
protection relay. It allows motor hp rating, full
load amps, efficiency and power factor to be
entered and will accurately calculate motor output
power. This is most useful with mag-drive pumps
or process applications where the process power
is desired over the utility power. Voltage, current
and power measurements can be displayed as well
as fault information and setpoints. The built-in
display simplifies troubleshooting and allows the
user to easily and precisely configure setpoints.
The 777-AccuPower can be used with SymCom’s
4-20mA output module to give an analog signal
proportional to output shaft power.
For more information see:
See Appendix A, page 66, Figure 1 for dimensional
drawing.
See Appendix B, page 71, Figures 1 & 2 for typical
wiring diagrams.
Specications
Model 777-AccuPower
3-phase current & voltage monitor, on-board display, calculates motor output power with
optional 4-20mA communications
Power Monitors
Standards Passed
Electrostatic Discharge (ESD) .....................IEC 61000-4-2, Level 3, 6kV contact, 8kV air
Radio Frequency Immunity (RFI), Conducted ......IEC 61000-4-6, Level 3 10V/m
Radio Frequency Immunity (RFI), Radiated ........IEC 61000-4-3, Level 3 10V/m
Fast Transient Burst ............................IEC 61000-4-4, Level 3, 3.5 kV input power
Short Circuit Rating .............................100kA
Surge
IEC ...........................................61000-4-5 Level 3, 2kV line-to-line;
Level 4, 4kV line-to-ground
ANSI/IEEE ...................................C62.41 Surge and Ring Wave Compliance
to a level of 6kV line-to-line
Hi-Potential Test ...............................Meets UL508 (2 x rated V + 1000V for 1 min.)
Vibration ......................................IEC 68-2-6, 10-55Hz, 1mm peak-to-peak,
2 hrs, 3 axis
Shock .........................................IEC 68-2-27, 30g, 3 axis, 11ms duration,
half-sine pulse
Safety Marks
UL ............................................UL508, UL1053
CE ............................................IEC 60947-1, IEC 60947-5-1
CSA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C22.2
Max. conductor size thru 777.. ....................0.65” with insulation
Dimensions ....................................3.05 H x 3.85 W x 5.05 D in.
(77.47 x 97.79 x 128.27 mm)
Weight ........................................1.3 lbs. (20.8 oz., 589.67 g)
Mounting Method ..............................Surface mount (4 - #8 screws) or
DIN rail mount
**On a well balanced system within recommended current range.
Input Characteristics
Line Voltage ...................................200-480VAC
Frequency .....................................50/60Hz
Motor Full Load Amp Range .....................2-800A (external CTs required
over 90A)
Functional Characteristics
TC- Overcurrent Trip Class ......................5, 10, 15, 20, 30
(J prefix enables jam protection
feature)
Output Characteristics
Output Contact Rating (SPDT - Form C)
Pilot duty ......................................480VA @ 240VAC
General purpose ................................10A @ 240VAC
General Characteristics
Ambient Temperature Range
Operating .....................................-40° to 70°C (-40° to 158°F)
Storage ........................................-40° to 80°C (-40° to 176°F)
Accuracy
Measured Horsepower/Kilowatt
Typical .....................................±3%**
Voltage .....................................±1%
Current .....................................±3%(<100 amps direct)
GF Current ..................................±15%
Timing .....................................5% ±1 second
Repeatability
Voltage .....................................±0.5% of nominal voltage
Current .....................................±1% (<100 amps direct)
Maximum Input Power ..........................10 W
Pollution Degree: ..............................3
Class of Protection: .............................IP20, NEMA 1 (finger safe)
Relative Humidity: .............................10-95%, non-condensing per IEC
68-2-3
Terminal Torque. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 in.-lbs.
CATALOG_SYMCOM_2014.indd 9 6/10/14 11:06 AM