Datasheet

www.symcom.com • 800-843-8848 • fax: 605-348-5685
14
Available Models:
Auxiliary Products:
777-P2 / 777-KW/HP-P2 Series units
Communication modules
Solutions Software
Features:
Displays:
Average current, individual line currents
and current unbalance
Current to ground
Average voltage, line-line voltages and
voltage unbalance
Instantaneous power
Power factor
Last four faults
All parameters programmed into 777
MotorSaver
®
Remaining restart delay times
Controls:
Start and stop buttons
Key lock input to prevent setpoint
changes
Change 777 setpoints from keypad
The RM-2000 is also equipped with a real-
time clock, which allows access to the
following motor management information
(most readings can be reset):
Total motor run-time
Time and date of last four faults, along
with voltage and current at time of trip
Time and date of last 10 motor starts
Total number of motor restarts
Minimum time between any two starts
with time and date
Run-time since last start
kWh consumed
kVARs consumed
A
pprovals:
RM-2000
RM-2000-CBM+
RM-2000-RTDW
Specications
The RM-2000
is a motor-monitoring device to be used in con-
junction with SymCom’s Model 777 family of
products (excluding the P1 Series), 77C family of
products and the Model 601 voltage monitors, via
Modbus protocol with a communications module.
The RM-2000/777 motor management system com-
bines unsurpassed electronic motor protection and
critical, user-friendly, motor monitoring.
The RM-2000 has membrane keypad controls
which allow both monitoring and control of a 777
MotorSaver
®*
through an RS-485 network using
Modbus RTU protocol. A second communication
port allows monitoring and control of up to 99
RM-2000 devices from a PLC, DCS, or SCADA
system or a PC with Solutions software installed.
The RM-2000 will act as a repeater for its motor
protector when accessed from the host computer or PLC. In addition to the monitoring functions,
the RM-2000 can be used to reset a tripped MotorSaver
®
or PumpSaver
®
.
The RM-2000 is easily mounted remotely and improves safety for service and operations personnel
by allowing them to control and monitor the device without opening the electrical cabinet. Using the
RM-2000 is a simple, cost-effective method for aiding compliance with arc flash safety regulations.
The enclosure and keypad assembly is water and ultraviolet light resistant.
For more information see:
See Appendix A, page 67, Figure 5 for dimensional drawing.
See Appendix B, page 72, Figure 6 for typical wiring diagrams.
Model RM-2000
remote monitoring, real-time clock, precise fault details, kwH
Remote Monitor
Maximum Input Power ............................. 3 W
Class of Protection .................................. NEMA 3R and/or UL Type 12
Relative Humidity .................................. Up to 85%, non-condensing
Safety Marks
UL ................................................ UL508
(File #E68520)
CSA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C22.2 No. 14 (File #46510)
CE ..............................................IEC 60947-6-2
Enclosure
Material ........................................... Black polycarbonate
Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Liquid crystal with extended temp. range
Size ............................................... 2 rows x 20 characters
Lighting ........................................... LED Backlight
Keypad ........................................... Eight 0.5” stainless steel dome buttons for
tactile feedback
Mechanical Life .................................... 100,000 actuations
Overlay Material ................................... Polyester
UV Exposure w/o degradation ....................... 2000 hrs.
Terminal Torque (depluggable terminal block) ........ 3 in.-lbs.
Dimensions ........................................ 6.4” H x 6.1” W x 1.1” D
(162.56 x 154.94 x 27.94mm)
Weight ............................................ 1.2 lbs. (19.2 oz., 544.31 g)
Mounting Method .................................. Surface mountable on backplane using
4 screws
Input Characteristics
Control Voltage .................................... 115VAC ±10%; 50/60Hz
Transient Protection
(Internal)
. . . . . . . . . . . . . . . . . . . . . . . . 2500V for 10ms
Functional Characteristics
Communication .................................... Port #1 for 777 Port #2 for PC, PLC, etc.
Baud Rate ......................................... 1200-28800 1200-28800
Setup ............................................. Even Parity None, Odd, or Even
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Stop Bit Parity 1 or 2 Stop Bits
Protocol ........................................... Modbus RTU Modbus RTU
Serial Interface ..................................... RS-485 RS-485
Available Addresses ................................ 01 A01-A99
Real-time Clock
Battery Back-up Life ................................ 10 years @ 25
°
C without external power
Last fault memory .................................. Stores up to 4 faults with time and date stamp,
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . includes voltages and currents at time of trip
Configuration ...................................... Two independent electro-mechanical
Form C (SPDT)
Contact Material. ................................... Silver/Tin Oxide
Output Characteristics
(RM-2000-RTDW version only)
Pilot Duty Rating. .................................. 240VA @ 120VAC
General Purpose Rating ............................. 5A @ 120VAC
General Characteristics
Ambient Temperature Range
Operating ......................................... -20
°
to 70
°
C (-4
°
to 158
°
F)
Storage. ........................................... -30
°
to 70
°
C (-22
°
to 158
°
F)
CATALOG_SYMCOM_2014.indd 14 6/10/14 11:06 AM