Datasheet
www.symcom.com • 800-843-8848 • fax: 605-348-5685
17
3-Phase Voltage Monitors
3-Phase Voltage Monitors
Pollution Degree ...............................3
Class of Protection ..............................IP20
Relative Humidity ..............................10-95%, non-condensing per IEC 68-2-3
Terminal Torque. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7in.-lbs.
Standards Passed
Electrostatic Discharge (ESD) .....................IEC 61000-4-2, Level 3, 6kV contact, 8kV air
Radio Frequency Immunity, Conducted ...........IEC 61000-4-6, Level 3 10V
Radio Frequency Immunity, Radiated .............IEC 61000-4-3, Level 3, 10 V/m
Fast Transient Burst .............................IEC 61000-4-4, Level 3, 3.5kV input power
Short Circuit Rating .............................100kA RMS, SYM, 600VAC max.
Surge Immunity
IEC ...........................................IEC 61000-4-5, Level 3, 2kV line-to-line;
Level 4, 4kV line-to-ground
ANSI/IEEE ....................................C62.41 Surge and Ring Wave Compliance to a
level of 6kV line-to-line
High Potential Test .............................Meets UL508 (2 x rated V +1000V for 1 minute)
Safety Marks
UL ............................................UL508 (File #E68520)
CE ............................................IEC 60947-1, IEC 60947-5-1
Max Conductor Size (with insulation) .............0.65”
Dimensions ....................................3.05 H x 3.85 W x 5.05 D in.
(77.47 x 97.79 x 128.27 mm)
Weight ........................................1.2 lbs. (19.2 oz., 544.31 g)
Mounting Method ..............................Surface mount (4 - #8 screws) or
DIN rail mount
All SymCom voltage monitors are microcontroller based and are factory calibrated for highly accurate
and precise voltage measurements to provide high sensitivity while minimizing nuisance tripping. The
high accuracy and precision of these devices allows them to detect a single-phase condition or voltage
unbalance even with regenerated voltages present. Uncalibrated devices require low sensitivity to voltage
faults to prevent nuisance trips, thus may not trip in the presence of regenerated voltages.
SymCom voltage monitors are built with transformer power supplies which makes them highly resistant
to damage caused by small voltage transients on the power system. Other types of power supplies such
as switching, resistor limited and capacitor limited, are typically more easily damaged by transients.
Product Selection Matrix
CATALOG_SYMCOM_2014.indd 17 6/10/14 11:06 AM