Datasheet

www.symcom.com • 800-843-8848 • fax: 605-348-5685
19
Available Models:
Features:
Low voltage trip
Single-phase trip
Reverse-phase trip
Fixed 6% voltage unbalance trip
Single LED diagnostics
Optional high voltage trip
Optional variable restart delay
Optional variable trip delay
Separate indicators for:
Power-up restart delay
Reverse-phase trip
Good voltage/relay energized
Unbalance/single-phase trip
High/low voltage tri
p
A
pprovals:
102A
102A-2
102A-3
102A-9
102-600
Specications
The Model 102A
is a 3-phase, auto-ranging, dual-range voltage
monitor that protects 190-480VAC, 50*/60Hz
motors regardless of size. The product provides
a user selectable nominal voltage setpoint and the
voltage monitor automatically selects between the
200V and 400V range.
A unique microcontroller-based voltage and
phase-sensing circuit constantly monitors the
3-phase voltages to detect harmful power line
conditions. When a harmful condition is detected,
the MotorSaver’s output relay is deactivated after
a specified trip delay. The output relay reactivates
after power line conditions return to acceptable
levels. The Model 102A includes advanced single
LED diagnostics. Five different light patterns
distinguish between faults and normal conditions.
For more information see:
See Appendix A, page 68, Figure 7 for dimensional
drawing.
See Appendix B, page 73, Figures 10 & 11 for typical
wiring diagrams.
Options
2 - Variable Restart Delay (Manual, 2-300 seconds)
3 - Variable Trip Delay (2-30 seconds)
9 - High Voltage Detection
Model 102A
3-phase voltage/phase monitor, high voltage option, panel mount, adjustable or manual
restart delay
3-Phase Voltage Monitor
Trip & Reset Accuracy ..........................±1%
Maximum Input Power .........................5 W
Terminal
Torque ........................................7 in.-lbs.
Wire Size ......................................12-18AWG
Standards Passed
Electrostatic Discharge (ESD) .....................IEC 61000-4-2, Level 3, 6kV contact, 8kV air
Fast Transient Burst ............................IEC 61000-4-4, Level 3, 4kV input,
2kV input/output
Transient Protection (Internal) ...................IEC 61000-4-5; 1995 ±6kV
Safety Marks
UL ..............................................UL508
(File #E68520)
CSA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22.2 No. 14 (File #46510)
CE ............................................IEC 60947-6-2
Dimensions ....................................2.93” H X 5.27” W X 2.95” D
(74.4 x 133.9 x 74.9mm)
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.05 lbs. (16.8 oz., 476.27 g)
Mounting Method ..............................#8 screws
Available Options
(2) Adjustable Restart Delay. . . . . . . . . . . . . . . . . . . . . .Manual, 2-300 seconds
(3) Adjustable Trip Delay ........................2-30 seconds
(Phasing and unbalance trip delay
remains at 2 seconds)
(9) High Voltage Operating Points
Trip (% of Setpoint) .............................110%
Reset (% of Setpoint) ............................107%
*Note: 50Hz will increase all delay timers by 20%.
Input Characteristics
Line Voltage
102A ..........................................190-480VAC
102-600 ........................................475-600VAC
Frequency .....................................50*/60Hz
Functional Characteristics
Low Voltage (% of setpoint)
Trip ...........................................90%
Reset ..........................................93%
Voltage Unbalance (NEMA)
Trip ...........................................6%
Reset ..........................................4.5%
Trip Delay Time
Low/High Voltage .............................4 seconds (standard)
Unbalance & Phasing Faults .....................2 seconds
Restart Delay Time
After a Fault ...................................2 seconds (standard)
After a Complete Power Loss ....................2 seconds (standard)
Output Characteristics
Output Contact Rating (SPDT - 1 Form C)
Pilot Duty .....................................480VA @ 240VAC
General Purpose ................................10A @ 240
VAC
General Characteristics
Temperature Range ...............................
-40
°
to 70
°
C (-40
°
to 158
°
F)
Ambient Temperature Range
Operating .....................................-40° to 70°C (-40° to 158°F)
Storage ........................................-40° to 80°C (-40° to 176°F)
CATALOG_SYMCOM_2014.indd 19 6/10/14 11:06 AM