Datasheet

www.symcom.com • 800-843-8848 • fax: 605-348-5685
21
Available Models:
Features:
Protects 3-phase motors from:
Loss of any phase (single phasing)
Low voltage
High voltage
Voltage unbalance
Phase reversal
Rapid cycling
8-pin plug-in; DIN rail or surface mountable
Manual reset option provides last fault
detection
Auto-ranging voltage
Advanced LED diagnostics
Adjustable voltage unbalance trip setting
Adjustable trip & restart delay settings
A
pprovals:
201A-AU
201-575-AU
201A-AU-OT (sold with OT08 socket)
201-575-AU-OT (sold with OT08 socket)
Specications
The Model 201A-AU
is a 3-phase, auto-ranging, dual-range voltage
monitor that protects 190-480VAC, 50/60Hz
motors regardless of size. The product provides
a user selectable nominal voltage setpoint and
the voltage monitor automatically selects between
the 200V and 400V range. The Model 201A-AU
includes advanced single LED diagnostics, where
five different light patterns distinguish between
faults and normal conditions. Adjustment knobs
allow the user to set a 1-30 second trip delay, a
manual restart or 1-500 second restart delay and a
2-8% voltage unbalance trip point.
This unique microcontroller-based voltage and
phase-sensing device constantly monitors the
3-phase voltages to detect harmful power line
conditions. When a harmful condition is detected,
the MotorSaver’s output relay is deactivated after
a specified trip delay. The output relay reactivates
after power line conditions return to acceptable
levels.
For more information see:
See Appendix A, page 68, Figure 8 for dimensional
drawing.
See Appendix B, page 74, Figures 14 & 15 for typical
wiring diagrams.
Auxiliary Products:
8-pin octal socket (P/N: CT0T08-PC)
Terminal Torque. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 in.-lbs.
Wire Gauge ....................................12-22 AWG Solid or stranded
Transient Protection (Internal) ...................2500V for 10 ms
Standards Passed
Electrostatic Discharge (ESD) .....................IEC 61000-4-2, Level 3, 6kV contact, 8kV air
Radio Frequency Immunity (RFI), Radiated ........150MHz, 10V/m
Fast Transient Burst .............................IEC 61000-4-4, Level 3, 3.5kV input power
& controls
Surge Immunity
IEC ............................................IEC 61000-4-5, Level 3, 4kV line-to-line;
Level 4, 4kV line-to-ground
ANSI/IEEE .....................................C62.41 Surge and Ring Wave Compliance to a
level of 6kV line-to-line
Hi-potential Test ................................Meets UL508 (2 x rated V + 1000V for 1 minute)
Safety Marks
UL (OT08-PC octal socket required) ...............UL508 (File #E68520)
CE ............................................IEC 60947-6-2
Dimensions ....................................1.750” H x 2.375” W x 4.125” D (with socket)
(44.45 x 60.325 x 104.775mm)
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.7 lbs. (11.2 oz., 317.51 g)
Mounting Method ..............................DIN rail or surface mount (plug in to
OT08-PC socket)
Socket Available ...............................Model OT08-PC (UL Rating 600V)
The 600V socket can be surface mounted or installed on DIN Rail.
Model 201A-AU
3-phase voltage/phase monitor, 8-pin socket mount, adjustable trip/restart delays &
voltage unbalance percentage
3-Phase Voltage Monitor
General Characteristics
Ambient Temperature Range
Operating .....................................-40° to 70°C (-40° to 158°F)
Storage ........................................-40° to 80°C (-40° to 176°F)
Trip & Reset Accuracy ..........................±1%
Maximum Input Power .........................5 W
Relative Humidity ..............................10-95%, non-condensing per IEC 68-2-3
Standards Passed
Electrostatic Discharge (ESD) .....................IEC 61000-4-2, Level 3, 6kV contact, 8kV air
Radio Frequency Immunity, Radiated .............150 MHz, 10V/m
Fast Transient Burst .............................IEC 61000-4-4, Level 3, 3.5kV input
power & controls
Surge
IEC ...........................................IEC 61000-4-5, Level 3, 4kV line-to-line;
Level 4, 4kV line-to-ground
ANSI/IEEE ....................................C62.41 Surge and Ring Wave Compliance
to a level of 6kV line-to-line
Hi-potential Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Meets UL508 (2 x rated V +1000V for 1 min.)
Safety Marks
UL (OT08-PC octal socket required) ...............UL508 (File #E68520)
CE ............................................IEC 60947-6-2
Enclosure ......................................Polycarbonate
Dimensions ....................................1.750” H x 2.375” W x 4.125” D (with socket)
(44.45 x 60.325 x 104.775mm)
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.7 lb. (11.2 oz., 317.51 g)
Mounting Method ..............................DIN rail or surface mount (plug in to
OT08-PC socket)
Socket Available ................................Model OT08-PC (UL Rating 600V)
The 600V socket can be surface mounted or installed on DIN Rail.
Input Characteristics
Line Voltage
201A-AU ......................................190-480VAC
201-575-AU ....................................475-600VAC
Frequency .....................................50/60Hz
Functional Characteristics
Low Voltage (% of setpoint)
Trip ..........................................90% ±1%
Reset .........................................93% ±1%
High Voltage (% of setpoint)
Trip ..........................................110% ±1%
Reset .........................................107% ±1%
Voltage Unbalance (NEMA)
Trip ..........................................2-8% adjustable
Reset .........................................Trip Setting Minus 1% (5-8%)
Trip Setting Minus 0.5% (2-4%)
Trip Delay Time
High, Low and Unbalanced Voltage ..............1-30 seconds adjustable
Single-Phasing Faults ...........................1 second fixed
Restart Delay Time
After a Fault ...................................Manual, 1-500 seconds adj.
After a Complete Power Loss ....................Manual, 1-500 seconds adj.
Output Characteristics
Output Contact Rating (1-Form C)
Pilot Duty .....................................480VA @ 240VAC, B300
General Purpose ................................10A @ 240VAC
Must use Model OT08-PC or RB08-PC
socket for UL Rating!
Note: Manufacturer’s recommended
screw terminal torque for the RB Series
and OT Series Octal Sockets is 12 in.-lbs.
CATALOG_SYMCOM_2014.indd 21 6/10/14 11:06 AM