Datasheet
www.symcom.com • 800-843-8848 • fax: 605-348-5685
25
Available Models:
Features:
• Low voltage trip
• Optional high voltage trip
• Single-phase trip
• Reverse-phase trip
• Fixed 6% voltage unbalance trip
• Single LED diagnostics
• Separate indications for:
• Power-up restart delay
• Reverse-phase trip
• Good voltage/relay energized
• Unbalance/single-phase trip
• High/low voltage trip
A
pprovals:
350-200
350-200-2
350-200-2-6
350-200-2-8**
350-200-2-9
350-400
350-400-2
350-400-2-5
350-400-2-6
350-400-2-8**
350-400-2-9
350-600
350-600-2
350-600-2-6
350-600-2-8**
350-600-2-9
Specications
The Model 350
is a heavy-duty voltage monitor. This product
should be used when high current relays or dual
contacts are required, or 480V controls are used.
Since the Model 350 uses heavy-duty relays, it
comes in fixed voltage range models rather than a
dual auto-ranging version like the Model 250.
The Model 350-200 has a 15A general purpose
contact. The Model 350-400 provides a SPDT (Form
C) relay rated to switch up to 600V, allowing the
use of 480V controls, eliminating the need for a
control power transformer to step the voltage
down to 120-240V. Several DPDT (two Form C
contacts) relay models are also available.
The Model 350 microcontroller-based family
of products are low cost yet highly advanced
solutions to heavy-duty problems. The Model
350 includes advanced single LED diagnostics.
Five different light patterns distinguish faults and
normal operating conditions. Other options such
as high voltage trip and adjustable restart delay
are available.
For more information see:
See Appendix A, page 68, Figure 7 for dimensional
drawing.
See Appendix B, page 75, Figure 20 for typical
wiring diagrams.
Options
2 - Variable Restart Delay (Manual, 2-300 seconds)
5 - DPDT Relay
6 - 2 Relays (1) 10A, (1) 15A
8 - 2 Relays (2) 15A
9 - High Voltage Detection
Model 350
3-phase voltage/phase monitor, panel mount, optional 1 or 2 15A rated
relay contacts
3-Phase Voltage Monitor
DPDT (-8 Option) ...............................2-15A General Purpose
480VA @ 240VAC Pilot Duty
1hp @ 240VAC
General Characteristics
Ambient Temperature Range
Operating .....................................-40° to 70°C (-40° to 158°F)
Storage ........................................-40° to 80°C (-40° to 176°F)
Trip & Reset Accuracy ..........................±1%
Maximum Input Power .........................5 W
Terminal
Torque ........................................7 in.-lbs.
Wire Size ......................................12-18AWG
Transient Protection (Internal) ...................IEC 61000-4-5;1995 ±6kV
Safety Marks
UL ............................................UL508 (File #E68520)
CSA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22.2 No. 14 (File #46510)
CE ............................................IEC 60947-6-2
Dimensions ....................................2.93”H x 5.27”W x 2.95”D
(74.4 x 133.9 x 74.9mm)
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.05 lbs. (16.8 oz., 476.27 g)
Mounting Method ..............................#8 screws
Special Options
Option 2 - Variable Restart Delay ................Manual, 2-300 seconds adj.
Option 5 - DPDT Relay
Option 6 - 2 Relays (1) 10A, (1) 15A
Option 8 - 2 Relays (2) 15A
Option 9 - High Voltage (% of setpoint)
Trip .........................................110%
Reset ........................................107%
*Note: 50Hz will increase all delay timers by 20%.
** These units are not equipped with Manual Reset.
Input Characteristics
Line Voltage
350-200 ........................................190-240VAC
350-400 ........................................380-480VAC
350-600 ........................................475-600VAC
Frequency .....................................50*/60Hz
Functional Characteristics
Low Voltage (% of setpoint)
Trip ...........................................90%
Reset ..........................................93%
Voltage Unbalance (NEMA)
Trip ...........................................6%
Reset ..........................................4.5%
Trip Delay Time
Low Voltage ...................................4 seconds
Unbalance & Phasing Faults .....................2 seconds
Restart Delay Time
After a Fault ...................................2 seconds
After a Complete Power Loss ....................2 seconds
Output Characteristics
Output Contact Rating
SPDT (350-200)
Pilot Duty .....................................480VA @ 240VAC
General Purpose ................................15A
SPDT (350-400, 350-600) .........................470VA @ 600VAC
DPDT (-6 Option) ...............................1-10A General Purpose
480VA @ 240VAC Pilot Duty
1-15A General Purpose
480VA @ 240VAC Pilot Duty
1hp @ 240VAC
CATALOG_SYMCOM_2014.indd 25 6/10/14 11:06 AM