Datasheet
www.symcom.com • 800-843-8848 • fax: 605-348-5685
27
Available Models:
Features:
• Load side monitoring of contactor
• Multiple LEDs for diagnostics, special
indicators for overvoltage, undervoltage and
phasing faults
• Prevents rapid cycling by monitoring
contactor or starter
• Infrared LED to communicate with
Informer-MS
A
pprovals:
455
455-480R
455-575
Specications
The Model 455
3-phase voltage monitor combines load and line
side monitoring to alert the user of contactor
failure or impending contactor failure. The
line side monitoring will protect the motor
from damaging line side conditions prior to the
motor starting. With other line-load side voltage
monitors, the motor must be started before a
voltage problem is detected. With the Model
455, the motor is fully protected at all times.
The motor will not start when a power problem
is present.
The Model 455 is a 3-phase, auto-ranging,
dual-range voltage monitor that protects 190-
480VAC, 50*/60Hz motors regardless of size.
The product provides a user selectable nominal
voltage setpoint and the voltage monitor automatically selects between the 200V and 400V
range. Other adjustments include a 2-30 second trip delay, a 2-300 second restart delay (and
manual restart) and a voltage unbalance trip point adjustment from 2-8%.
Four LEDs indicate the status of the Model 455: run light, undervoltage, overvoltage and
phasing fault. The Model 455 is a load and line side monitor that does not require a separate
power source for its electronics, making it much easier to install.
The Model 455 now has an infrared LED to communicate with the new Informer-MS. Just aim
the handheld diagnostic tool at the 455 to get valuable information such as real-time voltage
and voltage unbalance on both line and load sides, motor run hours, last 20 faults, last 32
motor starts, high and low voltage trip points, voltage unbalance trip point, restart and trip
delay settings, MotorSaver
®
status and more!
For more information see:
See Appendix A, page 68, Figure 7 for dimensional drawing.
See Appendix B, page 75, Figures 23 & 24 for typical wiring diagrams.
Auxiliary Products:
• Informer-MS
• IR Kit-36 (36” infrared adapter cable)
Model 455
3-phase voltage/phase monitor, panel mount, has add’l voltage inputs for monitoring load
side of contactor for contactor failure & works with Informer-MS diagnostic tool
3-Phase Voltage Monitor
Output Characteristics
Output Contact Rating (SPDT)
Pilot Duty .....................................480VA @ 240VAC
General Purpose ................................10A
High Voltage Relay (-480R)
Pilot Duty .....................................470VA @ 600VAC
General Characteristics
Ambient Temperature Range
Operating .....................................-40° to 70°C (-40° to 158°F)
Storage ........................................-40° to 80°C (-40° to 176°F)
Repeat Accuracy
Fixed Conditions ...............................±0.1%
Maximum Input Power .........................6 W
Terminal
Torque ........................................7 in.-lbs.
Wire Size ......................................12-18AWG
Transient Protection (Internal) ....................IEC 61000-4-5;1995 ±6kV
Safety Marks
UL ............................................UL508 (File #E68520)
CSA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C22.2 No. 14 (File #46510)
CE ............................................IEC 60947-6-2
Dimensions ....................................2.93”H x 5.27”W x 2.95”D
(74.4 x 133.9 x 74.9mm)
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.1 lbs. (17.6 oz., 498.95 g)
Mounting Method ..............................#8 screws
*Note: 50Hz will increase all delay times by 20%.
Input Characteristics
Line Voltage
455. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .190-480VAC
455-575 ........................................475-600VAC
455-480R. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .380-480VAC
Frequency .....................................50*/60Hz
Functional Characteristics
Low Voltage (% of setpoint)
Trip ...........................................90% ±1%
Reset ..........................................93% ±1%
High Voltage (% of setpoint)
Trip ...........................................110% ±1%
Reset ..........................................107% ±1%
Voltage Unbalance (NEMA)
Trip ...........................................2-8% adjustable
Reset ..........................................Trip setting minus 1%
Trip Delay Time
Low & High Voltage and Unbalance ..............2-30 seconds adjustable
Single-phasing Faults (>25% UB) .................2 seconds fixed
Restart Delay Time
After a Fault ...................................Manual, 2-300 seconds adj.
After a Complete Power Loss ....................Manual, 2-300 seconds adj.
After a Motor Shut-down ........................Manual, 2-300 seconds adj.
CATALOG_SYMCOM_2014.indd 27 6/10/14 11:06 AM