Datasheet
www.symcom.com • 800-843-8848 • fax: 605-348-5685
50
Available Models:
Features:
• Controls 12VDC alarm circuit (strobe light
and/or horn)
• Maintains 12VDC battery charge (fast
charge mode and maintenance mode)
• Trip delay timer
• Battery fault detection and reverse polarity
protection
• LED indicates unit’s status
• Press-to-test capability
A
pprovals:
Specications
The Model ACBC-120
is a dual purpose alarm controller/battery charging
unit. When there is a loss of 120VAC power,
the ACBC-120’s primary function as an alarm
controller activates. When this power loss occurs,
input power is switched to a 12VDC, lead-acid,
rechargeable backup battery and a 12VDC alarm
consisting of a strobe light and/or a horn is
activated. The horn follows a 2 second on/2 second
off pattern with a “horn silence” option to turn
the sound off. An LED indicator on the unit also
signals that the device has entered the alarm mode.
When 120VAC input is present the alarm circuit
can be tested and the unit’s secondary function as a
12VDC backup battery charger is activated. In fast
charge mode, the unit has the capability to source
up to 100mA of charging current. However, the
device normally charges at a current of 14mA in maintenance mode. The alarm circuit can be tested
by pressing the “test” button located on the front of the unit or by activating an external switch via
the “alarm contact” pin.
The device has the ability to signal low battery voltage if the voltage drops below 10.5VDC. The
device can also detect if no battery is present or if the battery is connected backwards. In either of
these cases, the ACBC-120 will signal a battery error and will not attempt to charge.
For more information see:
See Appendix A, page 68, Figure 8 for dimensional drawing.
See Appendix B, page 80, Figure 47 for typical wiring diagrams.
ACBC-120
ACBC-120-SD (sold with SD12-PC socket)
Auxiliary Products:
• 12-pin rectangle socket (P/N: SD12-PC)
Model ACBC-120
Alarm Controller and Battery Charger for pump control panels
Alarm Controller/Battery Charger
Standards Passed
Electrostatic Discharge (ESD) .....................IEC 61000-4-2, Level 3, 6kV contact, 8kV air
Radio Frequency, Radiated ......................150MHz, 10V/m
Fast Transient Burst .............................IEC 61000-4-4, Level 4, 4kV input lines;
4kV signal lines
Safety Marks
UL (SD12-PC socket required) ....................UL508 (File #E68520)
Dimensions ....................................1.750” H x 2.375” W x 4.125” D (with socket)
(44.45 x 60.325 x 104.775mm)
Weight ........................................0.7 lb. (11.2 oz., 317.51 g)
Mounting Method ..............................Surface mount with #8 or #10 screws
(plug into SD12-PC socket)
Socket Available ...............................Model SD12-PC (UL Rating 600V)
The 600V socket can be surface mounted
Input Characteristics
Supply Voltage
AC Input Voltage ...............................120V +10%
Frequency .....................................50/60Hz
AC Input Current ...............................0.018A (max.) 0.003 (typical)
AC Input Power ................................2.4W (max.) fast charge current
0.4W (typical) maint. charge current
Functional Characteristics
Battery Charging Characteristics
Acceptable Battery Type .........................12V lead-acid rechargeable
Fast Charge Current ............................100mA +10%
Maintenance Charge Current .....................14mA +50%
Low Battery Alert Level .........................10.5V
Output Characteristics
Strobe Light Alarm Output .......................12VDC@1A (max.)
Horn Alarm Output ..............................12VDC@1A (max.)
General Characteristics
Temperature Range .............................-40° to 60°C (-40° to 140°F)
Must use Model SD12-PC socket for UL Rating!
Note: Manufacturer’s recommended screw terminal torque for the SD Series Sockets is 12 in.-lbs.
CATALOG_SYMCOM_2014.indd 50 6/10/14 11:06 AM