Specifications
MOTORSAVER
®
201A-AU SPECIFICATIONS
Functional Characteristics
Low Voltage
Trip 90% of setting
Reset 93% of setting
High Voltage
Trip 110% of setting
Reset 107% of setting
Voltage Unbalance
Trip 2-8%
Reset Trip setting - 1% (5-8%)
Trip setting - 0.5% (2-4%)
Trip Delay
High/Low Voltage and Unbalance 1-30 seconds, adjustable
Single-Phasing 1 second, fixed
Restart Delay 1-500 seconds, adjustable; Manual
Input Characteristics
Line Supply Voltage
201A-AU 190-480VAC
201-575-AU 475-600VAC
Frequency 50/60Hz
Output Characteristics
Output Contact Rating
Pilot Duty 480VA @ 240VAC
General Purpose 10A @ 240VAC
General Characteristics
Environmental
Ambient Operating Temperature
1
-40° to 70°C (-40° to 158°F)
Relative Humidity 10-95%, non-condensing per IEC 68-2-3
Maximum Input Power 5 W
Standards Passed
Electrostatic Discharge (ESD) IEC 61000-4-2, Level 3, 6kV contact, 8kV air
Radio Frequency Immunity, Radiated 150 MHz, 10V/m
Fast Transient Burst IEC 61000-4-4, Level 4, 4kV input power and controls
Surge Immunity
IEC IEC 61000-4-5, Level 4, 4kV line-to-line; Level 4, 4kV
line-to-ground
ANSI/IEEE C62.41 Surge and Ring Wave Compliance to a level of
6kV line-to-line
Hi-Potential Test Meets UL508
(2 x rated V +1000 V for 1 minute)
Safety Marks
UL listed (OT08 octal socket required) UL508 (File #E68520)
CE IEC 60947-6-2
Dimensions 1.750” H x 2.375” W x 4.125” D (with socket)
Weight 9 oz.
Enclosure Polycarbonate
Mounting Method Plugs into OT08 Socket
Wire Gauge 12-22 AWG Solid or Stranded
Terminal Torque for P/N OT08 Socket 12 in. - lb
1
The ambient air temperature is the air temperature directly surrounding the product.
© 2010 SymCom, Inc. All Rights Reserved 9