3.3 SYSTEMRESET
Follow the steps below to reset the system from the CLI.
Procedure 25: Resetting the system using the CLI
Action Steps
Log in Press Enter.
At the username prompt, enter admin.
At the password prompt, enter password.
Reset system
Enter reset.
RESULT: The system responds Resetting, then immediately resets
both Ethernet Interfaces and all 4 T1/E1 interfaces without asking for a
confirmation.
end of procedure
Follow these steps to reset the system using the EMS.
Procedure 26: Resetting the system using the EMS
1. Select the File→Reset menu option.
RESULT: A confirmation window pops up.
2. To reset the system, select Yes.
NOTE: Selecting No cancels the action, and the system will not be reset.
Figure 22: EMS reset confirmation box
end of procedure