Control Inputs (X5)
At terminal X5 pins 2,3,4,5,6 and 7 there are six control inputs with HTL PNP characteristic available.
Control Input 1 (Ctrl. In 1) to Control Input 5 (Ctrl. In 5) are freely configurable in the COMMAND
MENU and are used for functions to be triggered externally. eg. for releasing the latching, resetting
the measurement result or for teaching the preset values or the analog output.
Control input 6 (Ctrl. In 6) is used exclusively for resetting the device parameters to the "default"
values. Thus, it is not freely configurable.
Note: With an HTL pulse (rising edge) on Ctrl. In 6, the device is reset to the factory
settings.
Wiring of the control inputs:
Unconnected control inputs are always “LOW”.
All inputs are designed to receive impulses from an electronic impulse source.
Notice for mechanical switching contacts:
When exceptionally mechanical contacts are used, please connect an external capacitor between
GND (-) and the corresponding input (+). A capacity of 10 µF will reduce the input frequency to
20 Hz and miscounting due to contact bouncing will be eliminated.