Continuation „Mode Frequency“:
WAIT TIME 1 (S)
This parameter defines the period time of the lowest frequency, accordingly the time between two rising
signal edges on channel A detecting frequency 0 Hz. Frequencies with a period time higher than the set
“WAIT TIME 1” will be detected as frequency = 0 Hz.
0,01
Frequency = 0 Hz, for frequencies below 100 Hz
1,00
Default value
79,99
Frequency = 0 Hz, for frequencies below 0,01 Hz
STANDSTILL TIME 1 (S)
This parameter defines the time setting for standstill definition. A time of xx.xx seconds after detection
"Frequency = 0 Hz " at channel A the unit signals "standstill" and reactivates the start-up-delays.
Stand still detection can be set in PRESELECTION MENU.
0,01
Shortest time in seconds
…
99,99
Largest time in seconds