Mode Counter
In this menu, the operation is defined as a position transducer for incremental signals (pulse, sum,
difference, up or down counter). Input A and B are active.
COUNT MODE
This parameter defines the counter operation.
0
A SINGLE
Input A is a counting input. Input B defines the counting direction:
„LOW“ = forward „HIGH“ = reverse
1
A + B
Sum counter: Impulses at A + Impulses at B
2
A - B
Differential counter: Impulses at A impulses at B
3
A/B 90 x1
Quadrature counter: Impulses A, B with edge counting x1
4
A/B 90 x2
Quadrature counter: Impulses A, B with edge counting x2
5
A/B 90 x4
Quadrature counter: Impulses A, B with edge counting x4
FACTOR A
Scaling factor for input A.
For example: A setting of factor 1.23456 and 100000 input pulses will result in a value of 123456 for input A.
0,00001
Smallest value
1
Default value
99,99999
Highest value
SET VALUE A
With a "RESET / SET COUNTER A" command (via control input), the counter of input A is set to this value.
-99999999
Smallest value
0
Default value
+99999999
Highest value
FACTOR B
Scaling factor for input B.
For example: A setting of factor 1.23456 and 100000 input pulses will result in a value of 123456 for input B.
0,00001
Smallest value
1
Default value
99,99999
Highest value
SET VALUE B
With a "RESET / SET COUNTER B" command (via control input), the counter of input B is set to this value.
-99999999
Smallest value
0
Default value
+99999999
Highest value
ROUND LOOP VALUE
Defines the number of encoder steps if a round-loop function is desired.
(Only for COUNT MODE: A SINGLE and A / B x 90)
0
Round-loop function is turned off.
99999999
Number of steps for the round-loop function.