Mode SSI
In this menu the operation is defined as absolute value converter (SSI signals).
SSI MODE
SSI Setting of the operating mode: Maser or Slave
Depending on the SSI MODE, different terminals must be used for the SSI CLK!
(Mode Master: Terminal X2 - Pin 1 and 2 / Mode Slave: Terminal X2 - Pin 5 and 6)
0
MASTER
Master-Mode: Clock for SSI encoder comes from the device
1
SLAVE
Slave-Mode: Clock for SSI encoder comes from the external master.
ENCODER RESOLUTION
Resolution of the SSI encoder (total number of bits)
10
Smallest value
25
Default value
32
Highest value
DATA FORMAT
Setting the SSI code (binary or gray)
0
GRAY CODE
SSI-Code Gray
1
BINARY CODE
SSI-Code Binär
BAUD RATE
Clock frequency of SSI telegrams
0
2 MHZ
N.A.
1
1.5 MHZ
N.A.
2
1 MHZ
Clock frequency 1 MHz
3
500 KHZ
Clock frequency 500 kHz
4
250 KHZ
Clock frequency 250 kHz
5
100 KHZ
Clock frequency 100 kHz
SSI ZERO
In the case of a "ZERO POSITION" command (via control input), the current SSI position of the encoder is
transferred to the "SSI ZERO" parameter and the actual encoder zero point is shifted accordingly. (Encoder zero
offset)
0
Smallest value
…
999999999
Highest value
HIGH BIT (for bit blanking)
Defines the highest evaluated bit (MSB) for bit blanking.
If all bits should be evaluated, HIGH BIT must be set to the given total number of bit.
01
Smallest value
25
Default value
32
Highest value