Continuation “Read Holding Registers und Write Multiple Registers”:
Access to actual data
Holding Register 0x1000 / 0x1001 hex and following allow access to variables of the device (actual
data registers):
Holding Register 0x1000 / 0x1001 hex Actual data with serial Code “:0” (Display value)
Holding Register 0x1002 / 0x1003 hex Actual data with serial Code “:1”
Holding Register 0x1004 / 0x1005 hex Actual data with serial Code “:2”
Holding Register 0x1006 / 0x1007 hex Actual data with serial Code “:3”
etc.
Access to status registers
Holding Register 0x2000 / 0x2001 hex and following allow access to status registers of the device:
Holding Register 0x2000 / 0x2001 hex Output Status (Ctrl. Out status, read only)
Holding Register 0x2002 / 0x2003 hex Serial Commands
Holding Register 0x2004 / 0x2005 hex External Command (Ctrl. In status, read only)
Holding Register 0x2006 / 0x2007 hex All Commands (read only)
Read Coils and Write Single Coil
With the functions “Read Coils” and “Write Single Coil” it is possible to read and set/reset single
commands:
Coil
number
Serial
code of
comma
nd
Command
0
54
RESET/SET
Transfer of the currently detected position value into the
parameter "Offset”
Setting Counter A and Counter B to "Set Value”
1
55
FREEZE DISPLAY
Freezing of the current measurement result
2
56
TEACH ANALOG START
Transfer of the current measurement result in the
parameter "Analog Start"
3
57
TEACH ANALOG END
Transfer of the current measurement result in the
parameter "Analog End"
4
58
TEACH PRESELECTION 1
Transfer of the current measurement result into the
parameter "Preselection 1"
5
59
TEACH PRESELECTION 2
Transfer of the current measurement result into the
parameter "Preselection 2"
6
60
TEACH PRESELECTION 3
Transfer of the current measurement result into the
parameter "Preselection 3"
7
61
TEACH PRESELECTION 4
Transfer of the current measurement result into the
parameter "Preselection 4"
8
62
TEACH PRESELECTION 5
Transfer of the current measurement result into the
parameter "Preselection 5"
9
63
TEACH PRESELECTION 6
Transfer of the current measurement result into the
parameter "Preselection 6"
10
64
RESET MIN/MAX
Reset the minimum / maximum value
11
65
LOCK RELEASE
Release latching of all outputs