Operating Manual touchMATRIX® Indicator AX350 Process indicator with two 16 bit analog inputs, touch screen and graphic display Product Features: Operating modes for visualization of input 1, input 2 or combinations of inputs (1+2, 1-2, 1x2, 1:2) Two universal 16 bit analog inputs for -10 … +10 V / 0 … 10 V / 0 … 20 mA / 4 … 20 mA High accuracy reference output 10 V for potentiometers > 1 kOhm Bright and high-contrast display with event-dependent color variations Emulation of a 7-segment display inclu
Version: AX350_01a_oi/cn/Jan-17 AX350_02a_oi/cn/Feb-17 AX350_02b_oi/cn/March-17 AX350_02c_oi/cn/Jul-17 AX350_3a_oi/cn/Okt-17 AX350_4a_oi/sn/April-18 Description First Version Second Version minor changes and fixes minor changes and fixes Expansion of the scale units Extension with IO-link Legal notices: All contents included in this manual are protected by the terms of use and copyrights of motrona GmbH.
Table of Contents 1. Safety Instructions and Responsibility................................................................................ 4 1.1 1.2 1.3 1.4 2 Introduction ........................................................................................................................ 6 2.1 2.2 3 Screen structure for parametrization ......................................................................................... 14 Screen structure in operation..........................................
1. Safety Instructions and Responsibility 1.1 General Safety Instructions This operation manual is a significant component of the unit and includes important rules and hints about the installation, function and usage.
1.3 Installation The device is only allowed to be installed and operated within the permissible temperature range. Please ensure an adequate ventilation and avoid all direct contact between the device and hot or aggressive gases and liquids. Before installation or maintenance, the unit must be disconnected from all voltage-sources. Further it must be ensured that no danger can arise by touching the disconnected voltage-sources.
2 Introduction This series of display unit is suitable for analog signals (-10 … 10V or 0/4 … 20 mA). It is very versatile in use, due to the intuitive handling and the extensive range of functions and options. 2.1 Operation mode All functions are can be configured in the parameter menu.
2.2 Function diagram Ax350_04a_oi_e.
3 Electrical Connections The terminal screws should be tightened with a slotted screwdriver (blade width 2mm). 3.1 DC Power Supply The unit accepts DC supply from 18 to 30 V at the terminals 1 and 2. The power consumption depends on the level of the supply voltage with aprox. 100 mA and the additional current required at the auxiliary voltage output. All GND terminals are internally interconnected. 3.
3.3 Analog Input The reference potential (AGND) for the analog inputs is connected at terminal 5. The unit provides two 16 bit analog inputs at terminal 6 and 7. The characteristics of the analog inputs (voltage input or current input ) can be set in the Menu IN 1/IN 2 PROPERTIES. Important: Before connecting the sensor the configuration (voltage or current input) must be set! Wiring of the intrecmental inputs: Voltage input 3.
3.5 Control Inputs The three control inputs at terminal 10, 11 and 12 have HTL PNP characteristics. In the COMMAND MENU the programmable functions for the control inputs can be assigned. Available functions are: reset the display value, display switching, locking the touch screen or release the lock function of the control or relay outputs. Wiring of the control inputs: Unconnected control inputs are always “LOW”. All inputs are designed to receive impulses from an electronic impulse source.
3.7 Serial interface (Option AO/AR/CO/CR) A serial interface (RS232 or RS485) is available at terminal 16, 17 und 18. This interface can be configured in the SERIAL MENU.
Wiring of the control-outputs: 3.9 AC Power supply (Option AC) The unit accepts AC supply from 115 to 230 V at the terminals 24 and 25. The power consumption depends on the level of the supply voltage with aprox. 3VA and the additional current required at the auxiliary voltage output. Devices with option AC can also be supplied with a DC voltage between 18 and 30 VDC at terminals 1 and 2. 3.
3.11 IO-Link (Option IO) An interface for connecting to an IO-Link master is available at terminal 34, 35 and 36. The display device (IO-link device) must always be connected to a separate power supply (AC or DC). The display device (IO-link device) can be operated in two ways. Display of 2 output process data (8 bytes): 2 output process data are sent by the IO-Link master cyclically. The two values can be parameterized or scaled in the Menu IO-LINK PROPERTIES.
4 Display and touch screen 4.1 Screen structure for parametrization The parameter menus and the parameters are described in chapter 5. Start setup procedure: To edit the parameters, press the touchscreen for 3 seconds. Menu selection: Select the parameter menu via arrow buttons and confirm with “OK”. The menu selection can be terminated with „C“. Parameter selection: Select the parameter via arrow buttons and confirm with „OK“. The parameter selection can be terminated with „C“.
4.2 Screen structure in operation The following screens are available during operation. Depending on the device version and the selected operation mode, not all displays will be shown. The source (IN1, IN2, …) for the single channel display and the two channel display are defined in the DISPLAY MENU. Single line display with unit and status bar To switch to the next display, press the touch screen. Control - or Relay status are only shown with Option AO, CO, RL.
5 Parameter / Overview-Menu Structure This section provides an overview of the menus and their parameters. The menu names are printed bold and the associated parameters are listed under the menu name. Depending on the device version and the selected operation mode, only the necessary menus / parameters are shown.
Menu / Parameter IO LINK PROPERTIES IN1 FACTOR IN1 DIVIDER IN1 ADDITIVE VALUE IN1 DECIMAL POINT IN1 SCALE UNITS IN2 FACTOR IN2 DIVIDER IN2 ADDITIVE VALUE IN2 DECIMAL POINT IN2 SCALE UNITS PRESELECTION VALUES PRESELECTION 1 PRESELECTION 2 PRESELECTION 3 PRESELECTION 4 PRESELECTION 1 MENU SOURCE 1 MODE 1 HYSTERESIS 1 PULSE TIME 1 OUTPUT TARGET 1 OUTPUT POLARITY 1 OUTPUT LOCK 1 START UP DELAY 1 EVENT COLOR 1 PRESELECTION 2 MENU SOURCE 2 MODE 2 HYSTERESIS 2 PULSE TIME 2 OUTPUT TARGET 2 OUTPUT POLARITY 2 OUTPUT
5.1 General Menu OPERATIONAL MODE This parameter specifies the selected measuring function.
5.2 IN 1 Properties This menu defines the parameter for input 1. CONFIGURATION This parameter defines the configuration of input 1. 0 1 2 -10 … 10 V 0 … 20 MA 4 … 20 MA -10 … 10 V 0 … 20 mA 4 … 20 mA START VALUE This parameter defines the dispay value of an input signal of 0V, 0mA or 4mA. Signal values between START VALUE and END VALUE behave proportional.
Continuation “IN 1 Properties”: SAMPLING TIME (S) The configured value corresponds to the sampling interval. This time interval in seconds defines the time between the single samples of the analog signals. This parameter directly affects the response time of the unit. 0,001 Shortest sampling time 0,01 60,000 Default value Longest sampling time AVERAGE FILTER Selectable average filter function to avoid measuring fluctuations.
5.3 IN 1 Linearization The linearization points of input 1 are defined in this menu. This menu is shown only, if the linearization is selected in 1 PROPERTIES. Linearization description and examples are shown in the appendix. P1(X) … P24(X) X-coordinate of the linearization point. This value representing the display value which the unit show in the display without linearization.
5.4 IN 1 Totalization The totalization function is defined in this menu. This menu will only be showed, if the totalization is active in Menu IN 1 PROPERTIES. The totalizator depends on the operation mode. See in the following list. Totalisation Operation mode INPUT 1 TOTAL INPUT 2 TOTAL LINKAGE TOTAL SINGLE aktiv 0 DUAL aktiv aktiv IN1 + IN 2 aktiv aktiv IN1 – IN 2 aktiv aktiv IN1 x IN 2 aktiv aktiv IN1 / IN 2 aktiv aktiv TIME BASE This parameter defines the time base of the totalization.
5.5 IN 2 Properties This menu defines the parameter for input 2.
5.6 IN 2 Linearization The linearization points of input 2 are defined in this menu. P1(X) … P24(X) X-coordinate of the linearization point, see IN 1Linearization. P1(Y) … P24(Y) Y-coordinate of the linearization point, see IN 1Linearization. 5.7 IN 2 Totalization The totalization function is defined in this menu. TIME BASE The time base of the totalization, see IN 1 Totalization DIVIDER The devisor for the totalization, see IN 1 Totalization.
5.8 Linkage Properties In this menu the parameters for the linked operation mode are defined. This menu is shown only, if in GENERAL MENU an operation mode (z.B. IN1 – IN2) with link was selected. The parameters in Menu IN 1 PROPERTIES and IN 2 PROPERTIES have to be set, before using a linked operation mode. The result of the link can be scaled with the following parameters. FACTOR This parameter defines the factor, the result of the link will be charged.
5.9 IO-Link Properties This menu defines the parameters for the display of the two output process data. This menu is only displayed if the device is equipped with the option IO (IO-Link Modul). IN1 FACTOR (Multiplication factor) This parameter defines the factor the received value is multiplied with. -99999999 Smallest value 1 Default value 99999999 Highest end value IN1 DIVIDER (Dividing factor) This parameter defines the factor the received value is devided by.
5.10 Preselection Values This menu is used to set the preselection values or the switching points. The preselection values / switching points are always referred to the display value. This menu is only available for devices with option CO, A0 or RL.
Continuation „Preselection 1 Menu“: The totalization depends on the operation mode. See chart in chapter IN 1 Totalization. MODE 1 Switching conditions for preselection 1.
Continuation „Preselection 1 Menu“: PULSE TIME 1 (S) Duration of output pulse for the switching condition of preselection 1 0,000 … 60,000 No output pulse (static signal) Pulse duration of 60 seconds OUTPUT TARGET 1 Assignment of an output or relay for the switching condition of preselection 1. If more than one switching condition is assigned to one output / relay, the output is set when at least one switching condition is true 0 NO No assignment 1 CTRL OUT 1 Switching condition assigned to “Ctrl.
5.12 Preselection 2 Menu SOURCE 2 The reference source for PRESELECTION 2, see PRESELECTION 1 MENU MODE 2 Switching conditions for preselection 2, see PRESELECTION 1 MENU (expect trailing preselection) 6 RES>=PRES-TRAIL See chapter PRESELECTION 1 MENU Trailing preselection 2: Display value is greater or equal to PRESELECTION 1 – PRESELECTION 2 PRESELECTION 2 is the trailing preselection from PRESELECTION 1.
5.13 Preselection 3 Menu SOURCE 3 The reference source for PRESELECTION 3, see PRESELECTION 1 MENU MODE 3 Switching conditions for preselection 3, see PRESELECTION 1 MENU (expect trailing preselection) 6 RES>=PRESTRAIL See chapter PRESELECTION 1 MENU Trailing preselection 3: Display value is greater or equal to PRESELECTION 4 – PRESELECTION 3 PRESELECTION 3 is the trailing preselection from PRESELECTION 4.
5.14 Preselection 4 Menu SOURCE 4 The reference source for PRESELECTION 4, see PRESELECTION 1 MENU MODE 4 Switching conditions for preselection 4, see PRESELECTION 1 MENU (expect trailing preselection) 6 RES>=PRESTRAIL See chapter PRESELECTION 1 MENU Trailing preselection 4: Display value is greater or equal to PRESELECTION 3 – PRESELECTION 4 PRESELECTION 4 is the trailing preselection from PRESELECTION 3.
5.15 Serial Menu This menu defines the basic settings of serial interface. This function is only available for devices with option CO or A0 UNIT NUMMER This parameter defines serial device addresses. The addresses between 11 and 99 can be assigned to the devices. Addresses with zero are not allowed, there are used as broadcast addresses.
Continuation „Serial Menu”: SERIAL PROTOCOL Determines the sequence of characters send, when using the serial output for cyclic data transmission under time control (xxxxxxx = value SERIAL VALUE). Setting „1“ removes the unit address from the string which allows a slight faster transmission cycle. 0 1 Transmission report = Unit Nr.
5.16 Analog Out Menu This menu defines the basic settings of the analog output. This function is only available for devices with option A0.
Continuation „Analog Out Menu“: ANALOG GAIN (%) This parameter specifies the maximum conversion of the analog output in %. e. g. 102.00 corresponds to a conversion of 10.2 V or 20.4 mA, when the ANALOG END value is reached. e. g. 95.00 corresponds to a conversion of 9.5 V or 18 mA, when the ANALOG END value is reached.. Smallest gain 0,00 100,00 110,00 Default value Highest gain ANALOG OFFSET (%) This parameter defines the zero offset of the analog output. z. B. 0.20 result in an offset of 0.02 V or 0.
5.17 Command Menu INPUT 1 ACTION This parameter defines the function of the input “Ctrl. In 1”. (s) = (d) = 0 1 2 NO TARA INPUT 1 TARA INPUT 2 3 TARA INPUT 1+2 4 5 RESET TOTAL 1 RESET TOTAL 2 6 RESET TOTAL 1+2 7 8 9 10 11 12 13 14 15 16 TEACH PRESEL. 1 TEACH PRESEL. 2 TEACH PRESEL. 3 TEACH PRESEL.
Continuation „Command Menu”: INPUT 1 CONFIG This parameter defines the switching characteristics of the input “Ctrl. In 1”. 0 ACTIVE LOW Active at „LOW“ (static) 1 ACTIVE HIGH Active at „HIGH“ (static) 2 RISING EDGE Activate at rising edge (dynamic) 3 FALLING EDGE Activate at falling edge (dynamic) INPUT 2 ACTION This parameter defines the function of the input “Ctrl. In 2”. See parameter INPUT 1 ACTION INPUT 2 CONFIG This parameter defines the switching characteristics of the input “Ctrl. In 2”.
Continuation „Display Menu:“ SOURCE DUAL TOP (Reference source for two-line display, first line) 0 1 2 3 4 INPUT 1 INPUT 2 LINKAGE 1 – 2 INPUT 1 TOTAL INPUT 2 TOTAL 5 LINKAGE TOTAL 6 7 8 9 10 11 IO LINK VALUE 1 IO LINK VALUE 2 MINIMUM VALUE 1 MAXIMUM VALUE 1 MINIMUM VALUE 2 MAXIMUM VALUE 2 the reference source is input 1 the reference source is input 2 the reference source is the result of the linking of input1 and input 2 the reference source is input 1 with totalization the reference source is input
Continuation „Display Menu:“ BRIGHTNESS (%) This parameter defines the brightness of the display in percent Min. brightness 10 Default value 80 Max. brightness 100 CONTRAST This parameter defines the viewing angle.. Viewing angle from top 0 Viewing angle from center 1 Viewing angle from bottom 2 SCREEN SAVER (S) This parameter defines the time in seconds until the display is switched off, after the last touch action. A new touch action will activate the display again.
6. Appendix 6.1. Data readout via serial interface All codes shown in the parameter SERIAL VALUE are available for serial readout by PC or PLC. For communication the monitors use the Drivecom Protocol according to ISO 1745. All protocol details can be found in our manual SERPRO which is available for download from our homepage www.motrona.com.
6.2 Display of scale units SCALE UNITS This parameter defines the required engineering unit. This parameter does not affect the calculation of the display value. The number of decimal places must be defined with the parameter DECIMAL POINT. 0 V Default 1 mV 2 A 3 mA 4 km/h 5 mph 6 feet/min 7 inch/min 8 g 9 kg 10 oz 11 W 12 kW 13 VA 14 mm 15 cm 16 m 17 inch 18 feet 19 C 20 F 21 K 22 1/sec 23 1/min 24 1/h 25 gal/min 26 Pa 27 kPa 28 % A customized unit with up to 16 digits can be edited using this parameter.
6.
Continuation „Parameterliste“: # 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 Menu IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION IN 1 LINEARIZATION
Continuation „Parameter“: # 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 Menue IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEARIZATION IN 2 LINEA
Continuation „Parameter“ # 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 Menue IN 2 TOTALIZATION IN 2 TOTALIZATION IN 2 TOTALIZATION IN 2 TOTALIZATION IN 2 TOTALIZATION IN 2 TOTALIZATION IN 2 TOTALIZATION LINKAGE PROPERTIES LINKAGE PROPERTIES LINKAGE PROPERTIES LINKAGE PROPERTIES LINKAGE PROPERTIES LINKAGE PROPERTIES LINKAGE PROPERTIES LINKAGE PROPERTIES IO LINK PROPERTI
Continuation „Parameter“ # 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 Menue PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 2 MENU PRESELECTION 3 MENU PRESELECTION 3 MENU PRESELECTION 3 MENU PRESELECTION 3 MENU PRESELECTI
Continuation „Parameter“ # 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 Menue ANALOG OUT MENU ANALOG OUT MENU ANALOG OUT MENU ANALOG OUT MENU ANALOG OUT MENU ANALOG OUT MENU ANALOG OUT MENU ANALOG OUT MENU COMMAND MENU COMMAND MENU COMMAND MENU COMMAND MENU COMMAND MENU COMMAND MENU COMMAND MENU COMMAND MENU COMMAND MENU COMMAND MENU DISPLAY MENU DISPLAY MENU DISPLAY MENU DISPLAY MENU DISPLAY MENU DISPLAY MENU DISPLAY MENU DISPL
Serial codes of commands: Serial Code 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 Ax350_04a_oi_e.
6.4 Linearization The linearization function of this unit allows converting a linear input signal into a non-linear developing (or vice versa). There are 24 programmable x/y coordinates available for input 1 and input 2, which can be set in any desired distance over the full conversion range. Between two coordinates, the unit uses linear interpolation. Therefore it is advisable to use more coordinates in a range with strong curves and only a few coordinates where the curvature is less.
Application Example: We like to display the filling quantity (volume) of a tank as shown below, with use of a pressure sensor mounted to the bottom of the tank. With this application the analogue pressure signal is proportional to the filling level, but not to the filling quantity. Volume P16_x P16_y P15_x P15_y P10_x P16_x Pressure P15_x 0-20 mA P07_y P01_y P10_x P01_x P10_y P01_x Pressure Sensor To solve the problem, we divide the non-linear part of the tank into 14 parts.
6.5 Dimensions Dimension in mm [inch] Ax350_04a_oi_e.
6.
Continuation “Technical specifications” Display: Type: Display range: Digit height: Color: Operation: Housing: Material: Mounting: Dimensions (w x h x d): Cut out (w x h): Protection class: Weight: Operation: Storage: EMC 2004/108/EC: LV 2006/95/EC RoHS 2011/65/EU: Ambient temperature: Conformity and standards: Ax350_04a_oi_e.