The following Operational Parameters provide scaling of the analog output:
Menu
Setting Range
Default
Analog-Begin:
Start value of the analog output.
-199999 ... 999999
0
Analog-End:
End value of the analog output.
-199999 ... 999999
10000
By means of these two parameters any window of the whole display range can be mapped onto
the analog output.
The subsequent example shows how to convert the display range from 1400 to 2200 into an
analog signal of 2 - 10 volts.
2
4
6
8
10
1000 2000 3000 4000 5000
Display Value
Volts
Analogue Output
A-ChAr = 0 - 10 V
AnAbEG = 1400
OFFSEt = 2.000
AnAEnd = 2200
GAin = 8.00
All settings refer to the scaled values which are shown in the display of the unit.