5.5.2. Printer-Mode
The Printer Mode allows cyclic or manual activation of transmissions of the specified register
data. The corresponding register can be specified by means of parameter „S-Code“.
Another parameter named „S-mod“ allows selection between two different string types:
„S-mod“
Transmission String Type
„Print1“
Space
Sign
Data
Line
feed
Carriage
return
+/-
X
X
X
X
X
X
LF
CR
„Print2“
Sign
Data
Carriage
return
+/-
X
X
X
X
X
X
CR
The mode of activation of serial transmissions can be determined as follows:
Cyclic (timed)
transmissions:
Set the Serial Timer to any value ≥ 0.010 sec.
Select the desired string type by parameter "S-mod"
After exit from the menu the timed transmissions will
start automatically
Manual activation of
transmissions
Set the Serial Timer to 0.000.
Select the desired string type by parameter "S-mod"
After exit from the menu a transmission can be activated at any time by
shortly pressing the ENTER key